Samson 3730 Series Mounting And Operating Instructions page 102

Electropneumatic positioner with hart communication
Table of Contents

Advertisement

Setting with TROVIS-VIEW software – Parameter list
Parameter
Positioner – Performance characteristics
Required propor-
tional-action coeffi-
cient KP (step)
Proportional-action
coefficient KP (step)
Required deriva-
tive-action time TV
(step)
Derivative-action
time TV (step)
Positioner – Fail-safe action
Fail-safe position
Positioner – Error control
Tolerance band
Delay time
Total valve travel
Limit of the total
valve travel
Alarm mode
102
EB 8384-3 EN
Values
Default
0...17
7
Off/1/2/3/4
2
Closing
0.1...10.0 %
5.0 %
0...9999 s
30 s
1
1000...
1 000 000
990 000 000
A1
A1 Conducting/high
Conducting/
A2 Non-conduc./low
high
A1 Non-conduc./low
A2
A2 Non-conduc./low
Conducting/
A1 Conducting/high
high
A2 Conduc./high
A1 Non-conduc./low
A2 Conducting/high
Description
Code 17
Code 17
Code 18
Code 18
Fail-safe action of the actuator upon air/auxil-
iary power failure or device start-up.
Determined during initialization by the position
of the slide switch (see section 5.1).
In double-acting actuators, the fail-safe position
relates only to the failure of the auxiliary power
supply. There is no defined position when the
supply air fails.
Code 19
Reset criterion for running control loop moni-
toring.
A control loop error is issued when the delay
time is exceeded and the system deviation is not
within the tolerance band.
Code 23
Code 24
Code 25