Status and diagnostic alarms
Status modification
The classification of the status alarms can be
changed as required.
They can be modified using TROVIS-VIEW
software over the local SSP interface.
In addition, the classification can be modi-
fied over the parameters in DD or easily en-
tered over the DTM.
Note!
+
All additional alarms generated by EXPERT
have the status "No alarm" by default.
Logging and displaying diagnostic
functions/alarms
The last 30 alarms are logged in the
positioner. However, it is important to note
that the same alarm is only logged once
when it first occurs.
The alarms and the condensed states ap-
pear on the display as described in the code
list (section 12).
In addition, the diagnostic parameters are
issued over the communication interface of
the positioner.
The diagnostic functions can easily be dis-
played and configured using the
TROVIS-VIEW software connected over the
local interface (SSP) or over the DTM.