Enable limit value
A1
Limit value A1
Enable limit value
A2
Limit value A2
Fault alarm with
"Function check"
condensed status
Fault alarm with
"Maintenance
alarm" or
"Maintenance re-
quired" condensed
status
Zero point limit
Positioner – Error control – Classification report
Condensed status error alarms
Note!
Each fault alarm has a status assigned to it.
The possible states are placed in order starting with the lowest priority:
Maintenance required
Maintenance demanded
Maintenance alarm
Function check
No alarm
The fault alarm present in the device with the highest priority determines which condensed status is dis-
played.
The condensed states "Maintenance required" and "Maintenance demanded" are also indicated on the
positioner display by
The condensed status "Maintenance alarm" causes the
play.
On/Off
On
0.0...100.0 %
2.0 %
On/Off
On
0.0...100.0 %
98.0 %
Yes/No
No
Maintenance
Maintenance
alarm only and
alarm
Maintenance
required only
0.0...100.0 %
5.0 %
Alarm is not added to the condensed status
.
Setting with TROVIS-VIEW software – Parameter list
Code 26
Code 26
Code 27
Code 27
Code 32
Code 33
Limit for zero point monitoring
Lowest
Highest priority
fault alarm symbol to appear on the dis-
103