Samson 3730 Series Mounting And Operating Instructions page 67

Electropneumatic positioner with hart communication
Table of Contents

Advertisement

For OPEN position:
1. Initialize positioner.
2. Use the MAN function to move the
positioner to 95 % (see LC display).
3. Adjust the tag (1) using the yellow ad-
justment screw (2) until the tag enters or
leaves the field of the proximity switch
(3).
You can measure the switching voltage
as an indicator.
Contact function:
Tag leaving the field > Contact is made.
Tag entering the field > Contact is opened.
Fig. 21 · Adjustment of the limit switch
Adjustment screw (2)
Tag (1) Proximity switch (3)
Adjusting the limit switch