Code list
44
y info
[0] OP
0 to 100 %
MAX
45
Solenoid valve info
Yes
No
46*
Polling address
0 to 63 [0]
ESC
Write protection HART
47*
YES [NO]
ESC
82
EB 8384-3 EN
Display only.
The control signal y is displayed in % in relation to the travel
range determined on initialization.
MAX : The positioner builds up its maximum output pressure
(refer to description for Codes 14 and 15).
0 P: The positioner vents the actuator completely
(refer to description for Codes 14 and 15).
– – –: The positioner has not been initialized.
Display only,
indicates whether a solenoid valve is installed.
If a voltage supply is connected at the terminals of the installed
solenoid valve, YES and HIGH appear on the display in alter-
nating sequence. If a voltage supply is not connected (actuator
vented, fail-safe position indicated on the display by the S
symbol), YES and LOW appear on the display in alternating se-
quence.
Select bus address
®
When the write protection function is activated, device data can
only be read, but not overwritten over HART
®
communication.