Mitsubishi Heavy Industries MHI FDU71VNXVF1 Technical Manual page 86

Inverter duct connected-high static pressure type air-conditioners
Hide thumbs Also See for MHI FDU71VNXVF1:
Table of Contents

Advertisement

1.10.2 Operation control function by the wired remote control
Model RC-E5
(1)
Switching sequence of the operation mode switches of remote control
(2)
CPU reset
This functions when "CHECK" and "ESP" buttons on the remote control are pressed simultaneously. Operation is same as that
of the power supply reset.
(3)
Power failure compensation function (Electric power supply failure)
(a) This becomes effective if "Power failure compensation effective" is selected with the setting of remote control function.
(b) Since it memorizes always the condition of remote control, it starts operation according to the contents of memory no
sooner than normal state is recovered after the power failure. Although the auto swing stop position and the timer mode are
cancelled, the weekly timer setting is restored with the holiday setting for all weekdays.
After recovering from the power failure, it readjusts the clock and resets the holiday setting for each weekday so that the
setting of weekly timer becomes effective.
(c) Content memorized with the power failure compensation are as follows.
Note (1) Items (vi), (vii) and (viii) are memorized regardless whether the power failure compensation is effective or not while the setting of silent mode is
cancelled regardless whether the power failure compensation is effective or not.
At power failure – Operating/stopped
(i)
If it had been operating under the off timer mode, sleep timer mode, the state of stop is memorized. (Although the
timer mode is cancelled at the recovery from power failure, the setting of weekly timer is changed to the holiday
setting for all weekdays.)
Operation mode
(ii)
Airflow volume mode
(iii)
Room temperature setting
(iv)
Louver auto swing/stop
(v)
However, the stop position (4-position) is cancelled so that it returns to Position (1).
"Remote control function items" which have been set with the remote control function setting ("Indoor function
(vi)
items" are saved in the memory of indoor unit.)
Upper limit value and lower limit value which have been set with the temperature setting control
(vii)
Sleep timer and weekly timer settings (Other timer settings are not memorized.)
(viii)
[Parts layout on remote control PCB]
SW2
SW2
A
B
M
SW1
S
SW1
X
Y
Master/ slave setting when more than one remote controls are used
A maximum of two remote controls can be connected to one indoor unit (or one group of indoor units.)
Indoor units
Note (1) Don't change SW2 because it is not used normally.
Remote control cord (no polarity)
Remote control
Remote control
SW1 "Master"
SW1 "Slave"
Caution
When using multiple remote controls, the following dispiays or settings
cannot be done with the slave remote control. It is available only with
the master remote control.
 Louver position setting (set upper or lower limit of swinging range)
 Setting indoor unit functions
 Setting temperature range
 Operation data display
 Error data display
 Silent mode setting
 Test operation of drain pump
 Remote control sensor setting
85
-
-
'12 • PAC-T-178
Switch
Setting
Contents
M
Master remote control
SW1
S
Slave remote control