POWER SOURCE 3N〜380ー415V 50Hz
TB
RD
L1
L1i
L1o
WH
L2
L2i
F(8A)
L2o
BL
L3
L3i
L3o
BK
N
Ni
No
NOISE FILTER
CN1
PWB3
GN
CN2-1
T12
GN
THo-IPM
THo-R2
THo-A
THo-S
TB
CNW
CNIP
CNB
TO INDOOR UNIT
(BK)
(Y)
(RD)
RD
1
BK
2
CNW2
POWER WIRES
1
2
BL
(OR)
CONTROL
3
SIGNAL WIRE
3
PWB1
52X1
52X3
52X6
LED1
LED2
BK
CNH
BK
(BR)
CNR
CNS
CNEEV1
(WH)
(RD)
(WH)
63H1
1
2
3
4
5 6
20S
CH
M
SM1
5 or 6 wires
Power cable, indoor-outdoor connecting wires
MAX over current
Power cable size
Model
(A)
100
16
125
18
140
19
The specifications shown in the above table are for units without heaters. For units with heaters, refer
to the installation instructions or the construction instructions of the indoor unit.
Switchgear of Circuit breaker capacity which is calculated from MAX. over current should be chosen
along the regulations in each country.
The cable specifications are based on the assumption that a metal or plastic conduit is used with no
more than three cables contained in a conduit and a voltage drop is 2%. For an installation falling
outside of these conditions, please follow the internal cabling regulations. Adapt it to the regulation
in effect in each country.
RD
WH
BL
1
3
BK
CT
52C
2
4
AC1
AC2
AC3
G
RD
R5
DM
K
+4
-6
R1
U
L
RD
RD
R2
R3
R4
THo-D
THo-R1
BL
52C
LPT
CNTH
CNM
CNPS
(WH)
(GR)
(WH)
18V
CNI 3
15V
CNI1
BL
(WH)
RD
CNA1
1
2
3
4
1 2
3
4
(WH)
BL
SW1
SW3
SW5
RD
CNA2
(WH)
BL
CNEEV2
CNFAN1
(RD)
(WH)
1
2
3
4
5 6
1
4
5
6 7
M
M
SM2
FMo1
5 or 6 wires
Power cable length
indoor-outdoor
Earth wire size
2
wire size x number
(mm)
(mm )
(m)
26
φ 1.6mm x 3
3.5
23
21
INVERTER
PWB2
GN
CNR
BK
(WH)
RD
U
U
MS
V
WH
IPM
3〜
RD
V
W
TB5
BL
P
+
W
C1
CM
WH
+
C2
BL
TB6
N
RD
CNW2
BL
(WH)
RD
CNW1
BK
(WH)
CNI2
(WH)
RD
CNO1
BL
(RD)
Local setting switch SW3(Set up at shipment OFF)
SW3-1
Defrost control change
φ 1.6
SW3-2
Snow guard fan control
SW3-3,4
Trial operation
Item
Description
CnA〜Z
Connector
CH
Crankcase heater
CM
Compressor motor
CT
Current sensor
DM
Diode module
F
Fuse
FM01
Fan motor
IPM
Intelligent power module
L
Reactor
LED1
Indication lamp(GREEN)
LED2
Indication lamp(RED)
LPT
Low pressure sensor
SM1
Expansion valve for cooling
SM2
Expansion valve for heating
Mark
Color
SW1
Pump down switch
BK
Black
SW3,5
Local setting switch
BL
Blue
TB
Terminal block
BR
Brown
THo-A
Thermistor(Outdoor air temp.)
GR
Gray
THo-D
Thermistor(Discharger pipe temp.)
P
Pink
THo-IPM
Thermistor(IPM)
OR
Orange
Thermistor(Heat exchanger pipe temp. )
THo-R1,2
RD
Red
THo-S
Thermistor(Suction pipe temp.)
WH
White
20S
Solenoid valve for 4 way valve
YE
Yellow
52X1
Auxilliary relay(for CH)
YE/GN
Yellow/Green
52X3
Auxilliary relay(for 20S)
52X6
Auxilliary relay(for 52C)
63H1
High pressure switch
The defrosting operation interval becomes shorter
by turning ON this switch. This switch should be
turned ON in the area where outside temperature
becomes below the freezing point.
When this switch is turned ON, the outdoor unit
fan will run for 30 seconds in every 10 minutes,
when outdoor temperature falls to 3 C or lower and
the compressor is not runnning when the unit is used
in a very snowy country, set this switch to ON.
Method of trial operation
1
Trial operation can be performed by using SW3-3,4.
2
Compressor will be in the operation when
SW3-3 is ON.
3
Cooling trial operation will be performed when
SW3-4 is OFF, and heating trial operation when
SW3-4 is ON.
4
Be sure to turn OFF SW3-3 after the trial operation
is finished.