Mitsubishi Heavy Industries MHI FDU71VNXVF1 Technical Manual page 106

Inverter duct connected-high static pressure type air-conditioners
Hide thumbs Also See for MHI FDU71VNXVF1:
Table of Contents

Advertisement

(4)
Outdoor unit fan control
(a) Outdoor unit fan tap and fan motor speed
Model
71
100
125, 140
(b) Fan tap control during Cooling/Defumidifying operation
Fan taps are selected depending on the outdoor unit heat exchanger temperature (Tho-R1, R2) and the outdoor air temperature (Tho-A).
Note (1) It is detected by Tho-R1 or R2, whichever the higher.
zone
Tap 5(6)
zone
Tap 5(6)
zone
Tap 4
zone
Tap 3
Note (1) Value in ( ) is for the 71 model.
zone
zone
15
18
(c) Fan tap control during heating operation
Fan taps are selected depending on the outdoor unit heat exchanger temperature (Tho-R1, R2) and the outdoor air temperature (Tho-A).
Note (1) It is detected by Tho-R1 or R2, whichever the lower.
zone
Tap 3
zone
Tap 3
zone
Tap 4
Note (1) Value in (
zone
3
Outdoor air temp. (˚C)
(d) Outdoor unit fan control at cooling low outdoor air
(i)
When all the following conditions are established after the start of compressor, the following control is implemented.
If the outdoor air temperature (Tho-A) is in the zone
seconds from the start of outdoor unit fan and the outdoor unit fan is at the tap 1 speed, the outdoor unit fan speed is
controlled according to the outdoor unit heat exchanger temperature (Tho-R1, R2).
Note (1) It is detected with Tho-R1 or R2, whichever the higher.
zone
5
Outdoor air temp. (˚C)
Mode
Cooling/Dehumidifying
Heating
Cooling/Dehumidifying
Heating
Cooling/Dehumidifying
Heating
zone
zone
zone
Tap 5(6)
Tap 5(6)
Tap 5(6)
Tap 4(6)
Tap 4
Tap 3
Tap 3
Tap 2
zone
zone
46
48
30
37
Outdoor air temp. (˚C)
zone
zone
zone
Tap 3
Tap 4
Tap 4(5)
Tap 5
Tap 5
Tap 6
) is for the 71 model.
zone
zone
12
15
9
zone
10
➀ speed ➁ speed ➂ speed ➃ speed ➄ speed ➅ speed ➆ speed
200
400
600
200
400
600
➀ speed ➁ speed ➂ speed ➃ speed ➄ speed ➅ speed ➆ speed
200
350
600
200
350
600
➀ speed ➁ speed ➂ speed ➃ speed ➄ speed ➅ speed ➆ speed
200
370
560
200
370
560
• Silent mode only
zone
Tap 4
zone
Tap 3
zone
Tap 2
zone
Tap 1
zone
zone
zone
20
30
Outdoor unit heat exchanger temp. (˚C)
• Silent mode only
zone
zone
Tap 3
zone
Tap 3
zone
Tap 4
zone
1
zone
-2
0
Outdoor unit heat exchanger temp. (˚C)
in the cooling/dehumidifying mode, it has elapsed 20
Retained
Outdoor unit fan speed
-10min
-1
20
Outdoor unit heat exchanger temp. (˚C)
105
-
-
Fan motor tap
710
810
850
710
810
850
740
820
870
740
820
870
640
745
870
640
800
870
zone
zone
Tap 5
Tap 5
Tap 5
Tap 5
Tap 5
Tap 3
Tap 4
Tap 3
Tap 3
Tap 3
Tap 3
Tap 2
zone
zone
43
53
33
40
zone
zone
Tap 3
Tap 3
Tap 3
Tap 5
Tap 5
Tap 6
zone
3
Outdoor unit fan speed
+10min
-1
30
'12 • PAC-T-178
-1
Unit: min
950
950
950
950
910
910
zone
zone
Tap 4
Tap 3
Tap 2
Tap 1