(a) Since it memorizes always the condition of remote control, it starts operation according to the contents of memory no
sooner than normal state is recovered after the power failure. Although the auto swing stop position and the timer mode are
cancelled, the weekly timer setting is restored with the holiday setting for all weekdays.
After recovering from the power failure, it readjusts the clock and resets the holiday setting for each weekday so that the
setting of weekly timer becomes effective.
(b) Content memorized with the power failure compensation are as follows.
Note (1) Items (vi), (vii) and (viii) are memorized regardless whether the power failure compensation is effective or not while the setting of silent mode is
cancelled regardless whether the power failure compensation is effective or not.
At power failure – Operating/stopped
(i)
If it had been operating under the off timer mode, sleep timer mode, the state of stop is memorized. (Although the
timer mode is cancelled at the recovery from power failure, the setting of weekly timer is changed to the holiday
setting for all weekdays.)
Operation mode
(ii)
Airflow volume mode
(iii)
Room temperature setting
(iv)
Louver auto swing/stop
(v)
However, the stop position (4-position) is cancelled so that it returns to Position (1).
"Remote control function items" which have been set with the remote control function setting ("Indoor function
(vi)
items" are saved in the memory of indoor unit.)
Upper limit value and lower limit value which have been set with the temperature setting control
(vii)
Sleep timer and weekly timer settings (Other timer settings are not memorized.)
(viii)
247
-
-
'12 • PAC-T-178