Mitsubishi Heavy Industries MHI FDU71VNXVF1 Technical Manual page 105

Inverter duct connected-high static pressure type air-conditioners
Hide thumbs Also See for MHI FDU71VNXVF1:
Table of Contents

Advertisement

(3)
Compressor soft start control
(a) Compressor protection start I
[Control condition] Normally, the compressor operation frequency is raised in this start pattern.
[Control contents] 1) Starts with the compressor's target frequency at A rps.
(b) Compressor protection start III
[Control condition] Number of compressor starts is only 1 counted after the power supply breaker ON.
[Control contents]
(i) Low frequency operation control during cooling/dehumidifying
[Control condition] Upon establishing the conditions of compressor protection start III, the low frequency
[Control contents]
(ii) Low frequency operation control during heating
[Control condition] When the conditions of compressor protection start III are established and one of following conditions
[Control contents]
However, when the ambient air temperature (Tho-A) is 35°C or higher during cooling/
dehumidifying or the indoor return air temperature (Th
starts at C rps.
2) At 30 seconds after the start of compressor, its target frequency changes to B rps and the
compressor is operated for 2 - 4 minutes with its operation frequency fixed at B rps.
Model
Operation mode
Cooling/Dehumidifying
71
Cooling/Dehumidifying
100
Cooling/Dehumidifying
125, 140
Operates by selecting one of following start patterns according to the operation mode and the
outdoor air temperature (Tho-A).
operation control is performed during cooling/dehumidifying.
a) Starts with the compressor's target frequency at A rps. When the outdoor air temperature
(Tho-A) is 35°C or higher, it starts at C rps.
b) At 30 seconds after the compressor start, the compressor's target frequency is changed to B
rps and the compressor's operation frequency is fixed for 10 minutes.
Model
71
Cooling/Dehumidifying
100
Cooling/Dehumidifying
125, 140
Cooling/Dehumidifying
a) is satisfied, the low number of revolutions operation control is performed during heating.
a) At 30 minutes or more after turning the power supply breaker on
a) Starts the compressor with its target frequency at A rps. However, when the indoor unit
return air temperature (Th
b) At 30 seconds after the start of compressor, the compressor's target frequency is changed to
B rps and the compressor's operation frequency is fixed for 10 minutes.
Model
71
100
125, 140
A rps
42
Heating
62
55
Heating
55
45
Heating
45
A
Operation mode
-A) is 25°C or higher, it start at C rps.
I
A
Operation mode
42
Heating
55
Heating
45
Heating
104
-
-
'12 • PAC-T-178
-A) is 25°C or higher during heating, it
I
B rps
C rps
42
62
55
55
45
45
B
rps
rps
42
42
55
55
45
45
B
rps
rps
42
55
45
40
40
30
30
25
25
C
rps
40
30
25
C
rps
40
30
25