Mitsubishi Heavy Industries MHI FDU71VNXVF1 Technical Manual page 341

Inverter duct connected-high static pressure type air-conditioners
Hide thumbs Also See for MHI FDU71VNXVF1:
Table of Contents

Advertisement

Remote control installation dimensions
Wiring outlet
(In case of embedding wiring)
12×7 Slot hole
Note: Installation screw for remote control
M4 Screw (2 pieces)
In case of exposing wiring
0.3mm
×2 cores.
2
L C D
Wiring specifications
(1) Wiring of remote control should use 0.3mm
(2) Maximum prolongation of remote control wiring is 600m.
If the prolongation is over 100m, change to the size below.
But, the wiring in the remote control case should be 0.3mm
Change the wire size outside of the case according to wire connecting. Waterproof treatment is
necessary at the wire
connecting section. Be careful about contact failure.
Length
100 to 200m
Under 300m
Under 400m
Under 600m
67
16
Installation hole
9×4.5 Slot hole (2 places)
X, Y Terminal block
70
Attach M3 screw
with washer
× 2 core wires or cables. (on-site configuration)
2
Wiring thickness
0.5mm
×2 cores
2
0.75mm
×2 cores
2
1.25mm
×2 cores
2
2.0mm
×2 cores
2
-
In case of embedding wiring
The remote control wiring can be extracted from the upper center.
After the thin part in the upper side of the remote control upper
case is scraped with a nipper or knife, remove burr with a file.
Upper case
Upper case
The peeling length of each wiring is as follows:
X wiring : 160mm
Y wiring : 150mm
2
(recommended) to 0.5mm
2
.
340
-
'12 • PAC-T-178
MITSUBISHI HEAVY INDUSTRIES,LTD.
AIR-CONDITIONING & REFRIGERATION SYSTEMS HEADQUARTERS
Wall surface
Wiring
Electrical box
(Prepare on site)
15
Thin part
Sheath
X Y
wiring
Sheath
Peeling length
Adapted to RoHS directive
Unit:mm