Mitsubishi Heavy Industries MHI FDU71VNXVF1 Technical Manual page 11

Inverter duct connected-high static pressure type air-conditioners
Hide thumbs Also See for MHI FDU71VNXVF1:
Table of Contents

Advertisement

Model
Item
Power source
Operation data
Nominal capacity
Power consumption
Running current
Power factor
Inrush current
Sound Pressure Level
dB(A)
Exterior dimensions
mm
Height × Width × Depth
Exterior appearance
(Munsell color)
Net weight
Refrigerant equipment
Compressor type & Q'ty
Starting method
Refrigerant oil
Heat exchanger
Refrigerant control
Air handling equipment
Fan type & Q'ty
Motor <Starting method>
Air flow (Standard)
CMM
External static pressure
Outside air intake
Air filter, Q'ty
Shock & vibration absorber
Insulation (noise & heat)
Electric heater
Remote control
Room temperature control
Safety equipment
Installation data
mm
Refrigerant piping size
Connecting method
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Refrigerant Quantity
Drain pump
Drain
IP code
Insulation for piping
Standard Accessories
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
Cooling
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation these value are somewhat higher due to
ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) The factory E.S.P. setting is set within the range of 80-150 Pa. If SW8-4 is turned to "ON", E.S.P. setting range can be
changed to 10-200 Pa.
(6) If wireless remote control is used, only 3-speed fan setting (Hi-Me-Lo) is available.
Indoor unit FDU140VF
Cooling
kW
14.0 [5.0 (Min.)~14.5 (Max.)]
kW
A
19.2 / 20.1
%
A
P-Hi : 47 Hi : 40 Me : 35 Lo : 30
280 × 1,370 × 740
kg
Louver fin & inner grooved tubing
Centrifugal fan × 3
W
100 + 200 <Direct line start>
P-Hi : 48 Hi : 35 Me : 28 Lo : 22
Pa
Standard : 60 Max : 200
Possible
Procure locally
Rubber sleeve (for fan motor)
Polyurethane form
W
wired : RC-EX1A, RC-E5 (option) wireless : RCN-KIT3-E (option)
Thermostat by electronics
Overload protection for fan motor
Frost protection thermostat
Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
Gas line
Flare piping
Max.30m (Outdoor unit is higher)
Max.15m (Outdoor unit is lower)
R410A 4.5kg in outdoor unit (incl. the amount for the piping of : 30m)
Built-in Drain pump
Hose Connectable with VP25 (I.D.25mm, O.D.32mm)
Drain hose
Outdoor air temperature
DB
WB
DB
27˚C
19˚C
35˚C
20˚C
7˚C
FDU140VNXVF
4.28
97
5 <Max.running current 30>
54
φ15.88 (5/8")
φ15.88 (5/8") × 1.0
:
Max.100m
IPXO
Necessary (both Liquid & Gas lines)
External static pressure of indoor unit
WB
24˚C
6˚C
0
-
-
'12 • PAC-T-178
Adapted to RoHS directive
Outdoor unit FDC140VNX
220-240V~50Hz / 220V~60Hz
Heating
16.0 [4.0 (Min.)~18.0 (Max.)]
4.42
19.8 / 20.7
97
Cooling : 49 Heating : 52
1,300 × 970 × 370
Stucco White
(4.2Y7.5/1.1) near equivalent
105
RMT5134MDE2 × 1
Direct line start
0.9 M-MA68
M shape fin & inner grooved tubing
Electronic expansion valve
Propeller fan × 2
86 × 2 <Direct line start>
100
0
Rubber sleeve (for Compressor)
20 (Crank case heater)
Internal thermostat for fan motor
Abnormal discharge temperature protection.
φ15.88 (5/8")
Flare piping
See page 33
Holes size φ20 × 3pcs
IPX4
Edging
Pa
60
PJG000Z044