Mitsubishi Heavy Industries MHI FDU71VNXVF1 Technical Manual page 15

Inverter duct connected-high static pressure type air-conditioners
Hide thumbs Also See for MHI FDU71VNXVF1:
Table of Contents

Advertisement

Symbol
A
B
C
D
E
223
310
60
15
61
D
150
580
150
880
Content
Service valve connection(gas side)
φ15.88(5/8")(Flare)
Service valve connection(liquid side)
φ9.52(3/8")(Flare)
Pipe/cable draw-out hole
φ20 × 3places
Drain discharge hole
Anchor bolt hole
M10 × 4places
E
27
32
88
Terminal block
B
A
165.5
25
Notes
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more the 15mm.
(3) Where the unit is subject to strong winds, lay it in such
a direction that the blower outlet faces perpendicularly
to the dominant wind direction.
(4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The model name label is attached on the lower right corner of the front panel.
Intake
L2
(  )
Service
space
Intake
Outlet
Minimum installation space
C
Examples of
installation
I I
Dimensions
L1
Open
Open
L2
300
250
L3
100
150
L4
250
250
L4
I I I
500
Open
100
250
Unit:mm