(i) Model FDC71VNX
1) Replace the PCB after elapsing 3 minutes from power OFF.
(Be sure to measure voltage (DC) between T26 and T27 on inverter PCB, and check that the
voltage is discharged sufficiently(10V or less). (Refer to Fig.1))
2) Disconnect the connectors from the control PCB.
3) Match the switches setting (SW4) with the former PCB.
4) Connect the connectors to the control PCB. (Confirm the connectors are not half inserted.)