Mitsubishi Heavy Industries MHI FDU71VNXVF1 Technical Manual page 23

Inverter duct connected-high static pressure type air-conditioners
Hide thumbs Also See for MHI FDU71VNXVF1:
Table of Contents

Advertisement

POWER SOURCE 1~220ー240V 50Hz/1~220V 60Hz
TB
F(30A)
F(8A)
RD
L1i
L1
1
WH
N
Ni
NOISE FILTER
2
E
GN
PWB3
E1
GN
L1o
No
YE/GN
CT
DM
+
-
P1
N1
INVERTER
CNI2
PWB2
(WH)
I P M
CNI4
(WH)
CNACT1
U
V
W
P2
N2
P
N2
(WH)
V
W
+
-
U
MS
A/F MODULE
P
3~
+
GN
N2
L1
L2
CM
L
Power cable, indoor-outdoor connecting wires
MAX over current
Power cable size
Model
2
(A)
(mm )
100
25
5.5
125
29
8
140
30
The specifications shown in the above table are for units without heaters. For units with heaters, refer
to the installation instructions or the construction instructions of the indoor unit.
Switchgear of Circuit breaker capacity which is calculated from MAX. over current should be chosen
along the regulations in each country.
The cable specifications are based on the assumption that a metal or plastic conduit is used with no
more than three cables contained in a conduit and a voltage drop is 2%. For an installation falling
outside of these conditions, please follow the internal cabling regulations. Adapt it to the regulation
in effect in each country.
TB
RD
1
WH
TO INDOOR UNIT
2
3
[
]
POWER WIRES
1
2
SIGNAL WIRE
3
F(4A)
SM1
M
6
4 3
2
1
CNW
CNW2
CNEEV1
(BK)
(OR)
(WH)
BL
CNI1
(WH)
CONTROL
BL
CNI3
PWB1
(WH)
52X1
52X3
LED1
52X2
RD
CNA2
BL
(WH)
RD
CNA1
CNF
CNR
CNS
CNH
CNTH
BL
(WH)
(BK)
(WH)
(RD)
(BR)
(WH)
DH
CH
20S
Optional
63H1
THo-R1
THo-D
THo-S
Power cable length
indoor-outdoor
Earth wire size
wire size x number
(m)
(mm)
24
φ1.6mm x 3
31
φ1.6
30
Mark
BK
BL
BR
GN
GR
P
SM2
FMO1
FMO2
OR
M
M
M
RD
WH
YE
YE/GN
6
4 3
2
1
7
6
5 4 1
7
6
5 4 1
CNEEV2
CNFAN1
CNFAN2
(RD)
(WH)
(WH)
ON
ON
OFF
OFF
1
2
3
4
1 2
3
4
LED2
SW1
SW3
SW5
CNIP
CNPS
CNB
(Y)
(WH)
(RD)
LPT
THo-A
THo-P
THo-R2
Local setting switch SW3(Set up at shipment OFF)
The defrosting operation interval becomes shorter
by turning ON this switch. This switch should be
SW3-1
Defrost control change
turned ON in the area where outside temperature
becomes below the freezing point.
When this switch is turned ON, the outdoor unit
fan will run for 30 seconds in every 10 minutes,
SW3-2
when outdoor temperature falls to 3℃ or lower and
Snow guard fan control
the compressor is not runnning when the unit is used
in a very snowy country, set this switch to ON.
Method of trial operation
1
Trial operation can be performed by using SW3-3,4.
2
Compressor will be in the operation when SW3-3 is ON.
SW3-3,4
Trial operation
3
Cooling trial operation will be performed when SW3-4 is OFF,
and heating trial operation when SW3-4 is ON.
4
Be sure to turn OFF SW3-3 after the trial operation
is finished.
Item
Description
Color
CnA~Z
Connector
Black
CH
Crankcase heater
Blue
DH
Drain pan heater
Brown
CM
Compressor motor
Green
CT
Current sensor
Gray
DM
Diode module
Pink
F
Fuse
Orange
FM01,02
Fan motor
Red
IPM
Intelligent power module
White
L
Reactor
Yellow
LED1
Indication lamp(GREEN)
Yellow/Green
LED2
Indication lamp(RED)
LPT
Low pressure sensor
SM1
Expansion valve for cooling
SM2
Expansion valve for heating
SW1
Pump down switch
SW3,5
Local setting switch
TB
Terminal block
THo-A
Thermistor(Outdoor air temp.)
THo-D
Thermistor(Discharge pipe temp.)
THo-P
Thermistor(IPM)
THo-R1,2
Thermistor(Heat exchanger pipe temp. )
THo-S
Thermistor(Suction pipe temp.)
20S
Solenoid valve for 4 way valve
52X1
Auxilliary relay(for CH)
52X2
Auxilliary relay(for DH)
52X3
Auxilliary relay(for 20S)
63H1
High pressure switch