Mitsubishi Heavy Industries MHI FDU71VNXVF1 Technical Manual page 111

Inverter duct connected-high static pressure type air-conditioners
Hide thumbs Also See for MHI FDU71VNXVF1:
Table of Contents

Advertisement

(g) Over-current protection current safe controls I, II
Detecting the outdoor unit inverter input (primary) current and the output (secondary) current, if the current values exceed
setting values, the compressor speed (frequency) is controlled to protect the inverter.
Retention
Reset
B
Current (A)
(Fig. C) The control value "A" and the reset value vary depending
on the compressor speed.
24
22
20
18
16
Reset valve B
14
12
40
50
60
Compressor speed (frequency) (rps)
(h) Power transistor temperature protection
(i) Protective control
If the power transistor temperature (detected with TIP) exceeds the setting value, the compressor speed (frequency)
is controlled to suppress the rise of power transistor temperature.
Reset
81(70)
Power transistor temp. (°C)
(i)
Anomalous power transistor current
(i) Prevents over-current on the inverter. If the current value in the power transistor exceeds the setting value, the
compressor stops.
(ii) If the current value in the power transistor exceeds the specified value and the compressor stops 4 times within 30
minutes, E42 is displayed on the remote control and it enters the anomalous stop mode.
(j)
Anomalous inverter PCB
If the power transistor detects any anomaly for 15 minutes, including the stop of compressor, E51 is displayed on the
remote control and it enters the anomalous stop mode.
(k) Anti-frost control by the compressor frequency control
(i) If the indoor unit heat exchanger temperature (detected with Th
start of compressor, the compressor speed (frequency) is controlled to initiate the anti-frost control of indoor unit
heat exchanger.
(ii) When there are 3 indoor unit heat exchanger temperatures (Th
Reduces compressor frequency
at each minute.
(iii) Regarding the anti-frost control by the operation stop, refer to the operation control function by the indoor unit
controller and the cooling, dehumidifying frost prevention of page 95.
Reduces frequency
at each minute.
A
Control valve A
70
80
90 100 110 120 130
Reduces compressor frequency
at each minute.
Retention
85(73)
Retention
1.5
3.5
Indoor unit heat exchanger temp. (°C)
-
Model
Control
value A
71
Primary
100
11.0 (23.0) 10.0 (22.0) 11.0 (23.0) 10.0 (22.0)
current
side
125,
11.0 (23.0) 10.0 (22.0) 11.0 (25.0) 10.0 (24.0)
140
71
Secandary
100
11.5 (Fig.C) 10.5 (Fig.C) 11.5 (Fig.C) 10.5 (Fig.C)
current
side
125,
11.5 (Fig.C) 10.5 (Fig.C) 11.5 (Fig.C) 10.5 (Fig.C)
140
Note (1) Value in ( ) are for the single phase models.
Note (1) Value in ( ) are for the single phase
100-140 models.
-R) exceeds the setting value at 4 minutes after the
I
-R), the lowest temperature is detected.
I
Reset
110
-
'12 • PAC-T-178
Cooling
Heating
Reset
Control
value B
value A
15.0
14.0
16.0
13.0
12.0
13.0
Reset
value B
15.0
12.0

Advertisement

Table of Contents
loading

Table of Contents