Mitsubishi Heavy Industries MHI FDU71VNXVF1 Technical Manual page 264

Inverter duct connected-high static pressure type air-conditioners
Hide thumbs Also See for MHI FDU71VNXVF1:
Table of Contents

Advertisement

2.10.4 Operation control function by the outdoor control
(1)
Determination of compressor speed (frequency)
Required frequency
Cooling/dehumidifying operation                        Unit: rps
( a )
Max. required
frequency
Min. required frequency
( b ) Heating operation                              Unit: rps
Max. required
frequency
Min. required frequency
( c )
If the indoor unit fan speed becomes "Me" or "Lo", Max required frequentcy goes down accordingly depending on indoor
unit model.
( d ) Max. required frequency under high outdoor air temperature in cooling mode
Maximum required frequency is selected according to the outdoor air temperature (Tho-A).
                                 Unit: rps
Max. required
frequency
(e)
Max. required frequency under outdoor air temperature in heating mode
Maximum required frequency is selected according to the outdoor air temperature (Tho-A).
                                 Unit: rps
Max. required
frequency
( f ) Selection of max. required frequency by heat exchanger temperature
(i) Maximum required frequency is selected according to the outdoor unit heat exchanger temperature (Tho-R) during
cooling/dehumidifying or according to the indoor unit heat exchanger temperature (Th
(ii) When there are 3 indoor unit heat exchanger temperatures (Th
                                 Unit: rps
Max. required
frequency
Note (1) Value in ( ) are for the 3 phase models.
(g) When any of the controls from ( a ) to ( f ) above may duplicate, whichever the smallest value among duplicated controls is
taken as the maximum required frequency.
(h) During heating, it is operated with the maximum required frequency until the indoor unit heat exchanger temperature
becomes 40°C or higher.
(2)
Compressor start control
( a )
Compressor starts upon receipt of the thermostat ON signal from the indoor unit.
( b ) However, at initial start after turning the power supply breaker, it may enter the standby state for maximum 30 minutes
("
PREPARATION" is displayed on the remote control) in order to prevent the oil loss in the compressor.
If the cooling/dehumidifying/heating operation is selected from the remote control when the outdoor unit is in the standby
state, "
PREPARATION" is displayed for 3 seconds on the remote control.
Model
Usual operation
Silent mode, outdoor temperature ≦15°C
Model
Usual operation
Silent mode
Model
Outdoor air temperature is
40°C or higher
Outdoor air temperature is
46°C or higher
Model
Outdoor air temperature is
18°C or higher
Model
Cooling/
Outdoor unit heat exchanger
dehumidifying
temperature is 56°C or higher
Indoor unit heat exchanger
Heating
temperature is 56°C or higher
100
125
90
105
60
80
20
20
100
125
90
105
60
80
20
20
100
125
75
90
75
75
100
125
60
80
-R), whichever the highest applies,
I
100
125
90
100
90
100
263
-
-
'12 • PAC-T-178
140
105
85
20
140
110
85
20
140
96
75
140
85
-R) during heating mode.
I
140
100
100