Mitsubishi Heavy Industries MHI FDU71VNXVF1 Technical Manual page 104

Inverter duct connected-high static pressure type air-conditioners
Hide thumbs Also See for MHI FDU71VNXVF1:
Table of Contents

Advertisement

1.10.4 Operation control function by the oudoor control
(1)Determination of compressor speed (frequency)
Required frequency
(a)
Cooling/dehumidifying operation
Max. required
frequency
Min. required frequency
Note (1) Value in ( ) are for the 3 phase models.
(b) Heating operation
Max. required
frequency
Min. required frequency
(c)
If the indoor unit fan speed becomes "Me" or "Lo", Max required frequency goes down
accordingly depending on indoor unit model.
(d) Max. required frequency under high outdoor air temperature in cooling mode
Maximum required frequency is selected according to the outdoor air temperature (Tho-A).
Max. required
frequency
(e)
Max. required frequency under outdoor air temperature in heating mode
Maximum required frequency is selected according to the outdoor air temperature (Tho-A).
Max. required
frequency
(f)
Selection of max. required frequency by heat exchanger temperature
(i) Maximum required frequency is selected according to the outdoor unit heat exchanger temperature (Tho-R) during
cooling/dehumidifying or according to the indoor unit heat exchanger temperature (Th
(ii) When there are 3 indoor unit heat exchanger temperatures (Th
Max. required
frequency
Note (1) Value in ( ) is for the 71 model.
(2) Value in 〔 〕 are for the 3 phase models.
(g) When any of the controls from (a) to (f) above may duplicate, whichever the smallest value among duplicated controls is
taken as the maximum required frequency.
(h) During heating, it is operated with the maximum required frequency until the indoor unit heat exchanger temperature
becomes 40°C or higher.
(2)
Compressor start control
(a)
Compressor starts upon receipt of the thermostat ON signal from the indoor unit.
(b) However, at initial start after turning the power supply breaker, it may enter the standby state for maximum 30 minutes
("
PREPARATION" is displayed on the remote control) in order to prevent the oil loss in the compressor.
If the cooling/dehumidifying/heating operation is selected from the remote control when the outdoor unit is in the standby
state, "
PREPARATION" is displayed for 3 seconds on the remote control.
Model
Usual operation
Silent mode, outdoor temperature ≦ 15°C
Model
Usual operation
Silent mode
Model
Outdoor air temperature is
40°C or higher
Outdoor air temperature is
46°C or higher
Model
Outdoor air temperature is
18°C or higher
Model
Cooling/
Outdoor unit heat exchanger
dehumidifying
temperature is 56(61)°C or higher
Indoor unit heat exchanger
Heating
temperature is 56(61)°C or higher
71
100
88
75
80
60
20
20
71
100
112
120
90
60
20
20
71
100
76
75
62
70
71
100
76
75
-R), whichever the highest applies,
I
71
100
60
75
60
100
103
-
-
'12 • PAC-T-178
Unit: rps
125
140
95(92)
95(92)
60
70
20
20
Unit: rps
125
140
120
120
70
70
20
20
Unit: rps
125
140
75
75
70
70
Unit: rps
125
140
80
85
-R) during heating mode.
I
Unit: rps
125
140
95 〔 92〕 95 〔 92〕
100
100