Data Point List For Rthd (Tracer Ch530) - Trane PIC Installation Operation Maintenance/ Programming

Protocol interface controller, modbus solution for trane chillers and rooftops
Table of Contents

Advertisement

Table 7 - Data Point List for RTHD chillers, Tracer CH530 controller
Data Type
Function
Binary
5/15
Outputs
Analog
6/16
Outputs
Binary Inputs
2
Analog Inputs
4
BAS-SVX08D-E4
Operation
Modbus Index
Offset
00001
0
00002
1
40001
0
40002
1
40003
2
40004
3
10002
1
30001
0
30002
1
30003
2
30004
3
30005
4
30006
5
30007
6
30008
7
30009
8
30010
9
30011
10
30012
11
30013
12
30014
13
30015-30016
14
30017-30018
15
Point Description
Chiller Enable/Disable Command (0=Disable)
Chiller Mode (0=Cool)
Copy of function 5/15 binary points
Chilled Water Setpoint
Current Limit Setpoint
Heating Setpoint
Chiller Running Status
Copy of function 2 binary points
Active Chilled/Hot Water Setpoint
Actual Capacity (Percent Run Load Amps)
Active Current Limit Setpoint
Evaporator Leaving Water Temperature
Evaporator Entering Water Temperature
Condenser Entering Water Temperature
Condenser Leaving Water Temperature
Chiller Status (See Appendix)
Compressor Running Outputs (See Appendix)
Evaporator Refrigerant Pressure Circuit 1
Evaporator Refrigerant Temperature Circuit 1
Condenser Refrigerant Pressure 1
Condenser Refrigerant Temperature 1
Starts - Compressor A
Run Time - Compressor A
Unit
bit
bit
bitfield
Temperature
Percentage
Temperature
bit
bitfield
Temperature
Percentage
Percentage
Temperature
Temperature
Temperature
Temperature
bitfield
bitfield
Pressure
Temperature
Pressure
Temperature
None
Hours
25