Trane PIC Installation Operation Maintenance/ Programming page 42

Protocol interface controller, modbus solution for trane chillers and rooftops
Table of Contents

Advertisement

Table 15 - Continued
Data
Modbus
Function
Type
Index
30054
30055
30056
30057
30058
30059
30060
Analog
30061
4
Inputs
30062
30063
30064
30065
30066
30067
30068
30069
30070
30071
30072
30073
30074
30075
30076
30077
30078
42
Operation
Offset
HVAC Unit Type ID
0 = CVHE/G
1 = CVHF
2 = CVHB
3 = CVGE
53
4 = CVAE
5 = RTHA
6 = RTHB
7 = two stage absorption
8 = one stage absorption
9 = direct fired absorption
54
Chiller Module Software Revision Level
55
Circuit Module Software Revision Level
56
Stepper Module 1 Software Revision Level
57
ABS: Stepper Module 2 Software Revision Level
58
Starter Module Software Revision Level
59
CTV: Purge Module Software Revision Level
60
Options Module Software Revision Level
61
Comm Module (TCI IV) Software Revision Level
62
Local Human Interface Software Revision Level
63
Remote Human Interface Software Revision Level
64
Front Panel Chilled Water Setpoint
65
CTV/RTH: Front Panel Current Limit Setpoint
66
CTV: Front Panel Hot Water Setpoint
67
CTV/RTH: Front Panel Ice Termination Setpoint
68
Design Delta Temperature
69
Differential To Start Setpoint
70
Differential To Stop Setpoint
71
CTV/RTH: Condenser Pressure Limit Setpoint
72
Chiller Power UP/Start Delay Setpoint
73
Rated Load Amps
74
Low Rfgt Temp Cutout
75
Leaving Water Temp Cutout
76
Setpoint Source Overide
77
CTV: Control Type: 0 = Chilled Water ;
1 = Hot Water ; 2 = Control Externally
Point Description
Unit
None
None
None
None
None
None
None
None
None
None
None
Temperature
Percentage
Temperature
Temperature
Temperature
Temperature
Temperature
Pressure
Temperature
Percentage
Temperature
Temperature
None
None
BAS-SVX08D-E4