Trane PIC Installation Operation Maintenance/ Programming page 45

Protocol interface controller, modbus solution for trane chillers and rooftops
Table of Contents

Advertisement

Table 16 - Continued
Data
Modbus
Function
Type
Index
10048
10049
10050
10051
10052
10053
10054
10055
10059
Binary
2
10060
Inputs
10061
10065
10066
10067
10068
10069
10070
10071
10072
30001
30002
30003
30004
30005
30006
30007
30008
30009
30010
30011
30012
30013
30014
30016
Analog
4
Inputs
30018
30019
BAS-SVX08D-E4
Operation
Offset
47
Supply Air Tempering is Active (1 = Yes 0 = No)
48
Exhaust Fan is Energized (1 = Yes 0 = No)
49
Condenser Fan A is Energized (1 = Yes 0 = No)
50
Condenser Fan B is Energized (1 = Yes 0 = No)
51
Heat Output 1 is Energized (1 = Yes 0 = No)
52
Heat Output 2 is Energized (1 = Yes 0 = No)
53
Reverse Valve is Energized (1 = Yes 0 = No)
54
Supply Fan is Energized (1 = Yes 0 = No)
58
Clogged Filter Local Input (1 = Yes 0 = No)
59
Compressor 2 Cycling Input (1 = OK 0 = Bad)
60
Compressor 1 Cycling Input (1 = OK 0 = Bad)
64
Default Defrost Flag
65
Demand Defrost Fault C Flag
66
Demand Defrost Fault B Flag
67
Demand Defrost Fault A Flag
68
Fan Failure (1 = Failed 0 = Ok)
69
Heat Failure (1 = Open 0 = Closed)
70
HPC for Compressor 2 (1 = High Press 0 = Normal)
71
HPC for Compressor 1 (1 = High Press 0 = Normal)
0
Outdoor Air Temperature Sensor Value
1
Zone Temperature Sensor Value
2
Mixed Air Temperature Sensor Value
3
Return Air Temperature Sensor Value
4
Local Zone Cooling Setpoint Input
5
Local Zone Heating Setpoint Input
6
Actual Zone Cooling Setpoint
7
Actual Zone Heating Setpoint
8
Outdoor Air Relative Humidity Sensor Value ( 10.0 to 90.0 %)
9
Return Air Relative Humidity Sensor Value ( 10.0 to 90.0 %)
10
Local Economizer minimum position Range ( 0.0 to 50.0 %)
11
Actual Economizer Damper Position Range ( 0.0 to 100.0 %)
12
Number of Cooling Stages Active ( 0 to 3)
13
Number of Heating Stages Active ( 0 to 3)
15
Reference Enthalpy Switch Settings ( 22, 23, 25 or 27 BTU/LBM)
Bit 0 Gas or Electric (1 = Gas Heat 0 = Electric Heat)
Bit 1 Heat Pump (Voyager I & II Only) (1 = Yes 0 = No)
Bit 2 Voyager III Unit (1 = Yes 0 = No)
17
Bit 3 Economizer Installed (1 = Installed 0 = Not Installed)
Bit 4 Gemini Unit (1 = Yes 0 = No)
Bit 5
Not Used - Reserved for UCP
Bit 6
Not Used - Reserved for UCP
Bit 7
Not Used - Reserved for UCP
Bit 0 Compressor On or Off (1 = On 0 = Off)
Bit 1 Compressor 1 Locked Out (1 = Yes 0 = No)
Bit 2 HPC for Compressor 1 (1 = High Press 0 = Normal)
18
Bit 3 Compressor 1 Cycling Input (1 = Normal 0 = Disabled)
Bit 4 Compressor 1 Exists (1 = Yes 0 = No)
Bit 5 Compressor 1 is Lead (1 = Yes 0 = No)
Bit 6
Not Used - Reserved for UCP
Bit 7
Not Used - Reserved for UCP
Point Description
Unit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Percentage
Percentage
Percentage
Percentage
None
None
None
bitfield
bitfield
45