Appendix - Trane PIC Installation Operation Maintenance/ Programming

Protocol interface controller, modbus solution for trane chillers and rooftops
Table of Contents

Advertisement

BAS-SVX08D-E4

Appendix

Table B - How to read Compressor Running Outputs in equipment data point lists
Compressor Running Outputs - bitfield
Bit Position
Bit 15
Not used
Bit 14
Not used
Bit 13
Compressor F running (1=On)
Bit 12
Compressor E running (1=On)
Bit 11
Compressor D running (1=On)
Bit 10
Compressor C running (1=On)
Bit 9
Compressor B running (1=On)
Bit 8
Compressor A running (1=On)
Bit 7
Not used
Bit 6
Not used
Bit 5
Compressor F exists (1=Yes)
Bit 4
Compressor E exists (1=Yes)
Bit 3
Compressor D exists (1=Yes)
Bit 2
Compressor C exists (1=Yes)
Bit 1
Compressor B exists (1=Yes)
Bit 0
Compressor A exists (1=Yes)
Table C - How to read Condenser Fan Running Outputs in equipment data point lists
Condenser Fan Running Outputs - bitfield
Bit Position
Bit 15
Condenser fan(s) H On (1=On)
Bit 14
Condenser fan(s) G On (1=On)
Bit 13
Condenser fan(s) F On (1=On)
Bit 12
Condenser fan(s) E On (1=On)
Bit 11
Condenser fan(s) D On (1=On)
Bit 10
Condenser fan(s) C On (1=On)
Bit 9
Condenser fan(s) B On (1=On)
Bit 8
Condenser fan(s) A On (1=On)
Bit 7
Condenser fan(s) H exists (1=Yes)
Bit 6
Condenser fan(s) G exists (1=Yes)
Bit 5
Condenser fan(s) F exists (1=Yes)
Bit 4
Condenser fan(s) E exists (1=Yes)
Bit 3
Condenser fan(s) D exists (1=Yes)
Bit 2
Condenser fan(s) C exists (1=Yes)
Bit 1
Condenser fan(s) B exists (1=Yes)
Bit 0
Condenser fan(s) A exists (1=Yes)
Description
Description
77