Data Point List For Rtac (Tracer Ch530) - Trane PIC Installation Operation Maintenance/ Programming

Protocol interface controller, modbus solution for trane chillers and rooftops
Table of Contents

Advertisement

Table 5 - Data Point List for RTAC chillers (Chiller Profile), Tracer CH530 controller
Data Type
Function
Binary
5/15
Outputs
Analog
6/16
Outputs
Binary Inputs
2
Analog Inputs
4
BAS-SVX08D-E4
Operation
Modbus Index
Offset
00001
0
00002
1
40001
0
40002
1
40003
2
40004
3
10002
1
30001
0
30002
1
30003
2
30004
3
30005
4
30006
5
30007
6
30008
7
30009
8
Point Description
Chiller Enable/Disable Command (0=Disable)
Chiller Mode (0=Cool)
Copy of function 5/15 binary points
Chilled Water Setpoint
Current Limit Setpoint
Heating Setpoint
Chiller Running Status
Copy of function 2 binary points
Active Chilled/Hot Water Setpoint
Actual Capacity (Percent Run Load Amps)
Active Current Limit Setpoint
Evaporator Leaving Water Temperature
Evaporator Entering Water Temperature
Condenser Entering Water Temperature
Condenser Leaving Water Temperature
Chiller Status (See Appendix)
Unit
bit
bit
bitfield
Temperature
Percentage
Temperature
bit
bitfield
Temperature
Percentage
Percentage
Temperature
Temperature
Temperature
Temperature
bitfield