Configuring The Uc600; Using The Bacnet Setup Tool; Connection; Configuration - Trane Tracer UC600 Integration Manual

For packaged outdoor air unit
Table of Contents

Advertisement

Configuring the UC600

Configuring the UC600 The UC600 BACnet configuration settings can be modified with either the
Trane BACnet Setup Tool or the Tracer TU service tool. The BACnet setup tool can only be used
to configure the baud rate, software device ID, and device units of measure. Tracer TU provides
complete configuration and programming capabilities.
This section provides information about the following:

Using the BACnet Setup Tool

Connection

To connect to the UC600:
1. Connect the universal serial bus (USB) cable between the laptop and the UC600, or to an
2. Click either the BACnet Setup Tool desktop icon or from the Start Menu navigate to All
3. Select the Direct Connection (USB cable) radio button, if it is not already selected.
4. Click the Connect button and the Unit Summary page displays after successful connection.

Configuration

At the Unit Summary page:
1. Enter a meaningful name for the controller.
2. Click the Controller Units expanding box label to display its contents.
3. Select the preferred units of measure for data communicated across the BACnet link.
4. Click the Protocol expanding box heading to display its contents.
5. Select the preferred Baud Rate in the drop-down list box.
6. If software Device ID is required, check the Use Software Device ID box and enter a BACnet
7. Click Save.
8. Cycle power to the device to have the new values take effect.

Using Tracer TU

This section describes how to first connect to the Tracer TU software and then configure the
UC600 controller.
N N o o t t e e s s : :
Connection
To connect to the UC600:
BAS-SVP18D-EN
"Using the BACnet Setup Tool," p. 9
"Using Tracer TU," p. 9
"MS/TP MAC Address," p. 10
"BACnet Device ID," p. 10
"BAS Unit Control," p. 11
equipment control panel USB port that is connected to the controller.
Programs/Trane/Tracer BACnet Setup Tool and select BACnet Setup Tool. The setup tool
splash screen displays briefly, followed by the Connect dialog box.
Device ID.
If Tracer TU is not installed, refer to the Tracer TU Service Tool Getting Started Guide
(TTU- SVN02). Tracer TU software, Version 8.2 or higher, is required.
The Tracer TU service tool screen interface often undergoes significant changes from
release to release. Please consult the Tracer TU Help for Programmable Controllers for
up to date information and procedures.
9

Advertisement

Table of Contents
loading

Table of Contents