Trane PIC Installation Operation Maintenance/ Programming page 39

Protocol interface controller, modbus solution for trane chillers and rooftops
Table of Contents

Advertisement

Table 15 - Continued
Data
Modbus
Function
Type
Index
10036
10037
10038
Binary
10039
2
Inputs
10040
10041
10042
10043
30001
30002
30003
30004
30005
30006
30007
30008
30009
30010
30011
Analog
30012
4
Inputs
30013
30014
30016
BAS-SVX08D-E4
Operation
Offset
35
external auto/stop
36
emergency stop
37
CTV: external free cooling
38
CTV/RTH: external ice making
39
CTV: external heat pump
40
Manual Chilled Water Pump (1= ON; 0 = AUTO)
41
External Input Type (0 = 4-20mA; 1 = 2 - 10V)
42
CTV: Manual Oil Pump (1= ON, 0 = AUTO)
0
Leaving Chilled Water Temperature
1
Entering Chilled Water Temperature
2
Condenser Leaving Water Temperature
3
Condenser Entering Water Temperature
4
Average % Current Draw
5
Operating Code
6
Last Active Diagnostic Code
7
Active Chilled Water Setpoint
8
copy of function 2 binary points 10001 to 10011
9
Last Operating Mode at Time of Last Diag
Bit 0 UNUSED
Bit 1 UNUSED
Bit 2 UNUSED
10
Bit 3 Limit Warning (1=Warning)
Bit 4 Chilled Water Pump (1 = On, 0 = Off)
Bit 5 Condenser Water Pump (1 = On, 0 = Off)
Bit 6 Compr/Unit Running (1 = Yes, 0 = No)
Bit 7 Alarm (1 = On, 0 = Off)
Bit 0 UNUSED
Bit 1 UNUSED
Bit 2 UNUSED
11
Bit 3 UNUSED
Bit 4 UNUSED
Bit 5 CTV/RTH: Actively Ice Making (1 = Yes, 0 = No)
Bit 6 Reset Relay (1 = On, 0 = Off)
Bit 7 CTV/ABS: Max Capacity (1 = Yes, 0 = No)"
Bit 0 Chilled Water Flow (1 = On, 0 = Off)
Bit 1 Condenser Water Flow (1 = On, 0 = Off)
Bit 2 MMR exits
12
Bit 3 MAR exits
Bit 4 IFW exists
Bit 5 RESERVED
Bit 6 RESERVED
Bit 7 RESERVED
13
Active Outdoor Air Temperature
Bit 0 RESERVED
Bit 1 RESERVED
Bit 2 Tracer
Bit 3 External Direct Capacity Control
Bit 4 future 2
Bit 5 future 1
Bit 6 External Input
Bit 7 Front Panel"
15
CTV/RTH: Active Ice Termination Setpoint
Point Description
Unit
bit
bit
bit
bit
bit
bit
bit
bit
Temperature
Temperature
Temperature
Temperature
Percentage
None
None
Temperature
bitfield
None
bitfield
bitfield
bitfield
Temperature
bitfield
Temperature