Trane PIC Installation Operation Maintenance/ Programming page 44

Protocol interface controller, modbus solution for trane chillers and rooftops
Table of Contents

Advertisement

Table 16 - Continued
Data
Modbus
Function
Type
Index
40009
Analog
6/16
Outputs
40010
40011
10004
10005
10006
10007
10008
10009
10010
10011
10012
10013
10014
10015
10016
10017
10019
10020
10021
10022
10023
10024
Binary
2
10025
Inputs
10026
10027
10028
10030
10031
10032
10033
10034
10035
10036
10037
10038
10039
10040
10041
10042
10043
10045
10046
10047
44
Operation
Offset
Bit 0 Compressor Lockout (Lockout Both) (1 = Not Locked Out 0 = Lock Out)
Bit 1 Auxiliary Heat Lockout (1 = Not Locked Out 0 = Lock Out)
Bit 2 Lead/Lag Enable/Disable (1 = Enabled 0 = Disabled)
8
Bit 3 Zone Temperature Source (1 = Echelon 0 = Local)
Bit 4 Economizer Min Position Setpoint Source (1 = ICS 0 = Local)
Bit 5 Power Exhaust Setpoint Source (1 = ICS 0 = Local)
Bit 6 Reset Select Input Source (VAV Only) (1 = ICS 0 = Local)
Bit 7 Tracer Has Not Written (1 = Yes 0 = No)
9
Reserved for BAS 1
10
Reserved for BAS 2
3
Gemini Unit (1 = Yes 0 = No)
4
Economizer Installed (1 = Installed 0 = Not Installed)
5
Gas or Electric (1 = Gas Heat 0 = Electric Heat)
6
Heat Pump (Voyager I & II Only) (1 = Yes 0 = No)
7
Compressor 1 Exists (1 = Yes 0 = No)
8
Compressor 1 Cycling Input (1 = Normal 0 = Disabled)
9
HPC for Compressor 1 (1 = High Press 0 = Normal)
10
Compressor 1 Locked Out (1 = Yes 0 = No)
11
Compressor On or Off (1 = On 0 = Off)
12
Compressor 2 Exists (1 = Yes 0 = No)
13
Compressor 2 Cycling Input (1 = Normal 0 = Disabled)
14
HPC for Compressor 2 (1 = High Press 0 = Normal)
15
Compressor 2 Locked Out (1 = Yes 0 = No)
16
Compressor On or Off (1 = On 0 = Off)
18
Return Humidity Sensor Failed (1 = Yes 0 = No)
19
Return Air Temperature Sensor Failed (1 = Yes 0 = No)
20
Outdoor Humidity Sensor Failed (1 = Yes 0 = No)
21
Supply Air Temperature Sensor Failed (Mixed) (1 = Yes 0 = No)
22
Outdoor Air Temperature Sensor Failed (1 = Yes 0 = No)
23
Zone Temperature Sensor Failed (1 = Yes 0 = No)
24
Economizer Fault (1 = Yes 0 = No)
25
Coil Temperature Sensor Failed (1 = Yes 0 = No)
26
Local Zone Cooling Setpoint Failed (1 = Yes 0 = No)
27
Local Zone Heating Setpoint Failed (1 = Yes 0 = No)
29
Filter Clogged Failure (1 = Yes 0 = No)
30
Heat Failure (1 = Yes 0 = No)
31
High Temperature Input is Hot / Smoke Detector (1 = Yes 0 = No)
32
Heat Stage 3 Exists (1 = Yes 0 = No)
33
Heat Stage 2 Exists (1 = Yes 0 = No)
34
Not Used - Reserved for UCP (1 = Yes 0 = No)
35
Emergency Heat Mode (Heat Pump Only) (1 = Yes 0 = No)
36
Supply Fan Mode (1 = On 0 = Auto)
37
Manual/Auto Mode (1 = Manual 0 = Auto)
38
Heat/Cool Mode (1 = Cool 0 = Heat)
39
Off Mode (1 = Off 0 = Auto)
40
Timed Override Request (1 = Yes 0 = No)
41
Test Mode in Progress (1 = Yes 0 = No)
42
Decision to Economize (1 = Enabled 0 = Disabled)
44
Power Up Failure has Occurred (1 = Yes 0 = No)
45
Heat Pump Defrost is Active (1 = Yes 0 = No)
46
Evaporator Defrost is Active (1 = Yes 0 = No)
Point Description
Unit
bitfield
None
None
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
BAS-SVX08D-E4