Table 9 - Data Point List for CGAN/CXAN/CGAM/CXAM/CGC/CCUH/CCUN/CGWH/CGWN/RAUL chillers, Tracer CH530 controller
Data Type
Function
Binary
5/15
Outputs
Analog
6/16
Outputs
Binary Inputs
2
Analog Inputs
4
BAS-SVX08D-E4
Installation
Modbus Index
Offset
00001
0
00002
1
40001
0
40002
1
40003
2
40004
3
10002
1
30001
0
30002
1
30003
2
30004
3
30005
4
30006
5
30007
6
30008
7
30009
8
30010
9
30011
10
30012
11
30013
12
30014
13
30015
14
30016
15
30017
16
30018
17
30019
18
30020
19
30021-30022
20-21
30023-30024
22-23
30025-30026
24-25
30027-30028
26-27
30029-30030
28-29
30031-30032
30-31
30033-30034
32-33
30035-30036
34-35
30037-30038
36-37
30039-30040
38-39
30041-30042
40-41
30043-30044
42-43
Point Description
Chiller Enable/Disable Command (0=Disable)
Chiller Mode (0=Cool)
Copy of function 5/15 binary points
Chilled Water Setpoint
Current Limit Setpoint
Heating Setpoint
Chiller Running Status
Copy of function 2 binary points
Active Chilled/Hot Water Setpoint
Actual Capacity (Percent Run Load Amps)
Active Current Limit Setpoint
Evaporator Leaving Water Temperature
Evaporator Entering Water Temperature
Condenser Entering Water Temperature
Condenser Leaving Water Temperature
Chiller Status (See Appendix)
Compressor Running Outputs (See Appendix)
Condenser Fan Running Outputs (See Appendix)
Outdoor Air Temperature
Evaporator Refrigerant Pressure Circuit 1
Evaporator Refrigerant Pressure Circuit 2
Evaporator Refrigerant Temperature Circuit 1
Evaporator Refrigerant Temperature Circuit 2
Condenser Refrigerant Pressure 1
Condenser Refrigerant Pressure 2
Condenser Refrigerant Temperature 1
Condenser Refrigerant Temperature 2
Starts - Compressor A
Run Time - Compressor A
Starts - Compressor B
Run Time - Compressor B
Starts - Compressor C
Run Time - Compressor C
Starts - Compressor D
Run Time - Compressor D
Starts - Compressor E
Run Time - Compressor E
Starts - Compressor F
Run Time - Compressor F
Unit
bit
bit
bitfield
Temperature
Percentage
Temperature
bit
bitfield
Temperature
Percentage
Percentage
Temperature
Temperature
Temperature
Temperature
bitfield
bitfield
bitfield
Temperature
Pressure
Pressure
Temperature
Temperature
Pressure
Pressure
Temperature
Temperature
None
Hours
None
Hours
None
Hours
None
Hours
None
Hours
None
Hours
27