Table 4. Section dimensions (inches) and weights (pounds) - unit sizes 30-100
1
Nominal airflow
2
Airflow at 625 fpm
Unit size
Height (inches)
Width (inches)
Coil, small
with 2-row UW
Coil, medium
with 8-row UW
Coil, extended-medium
with 8-row UW
Coil, medium-large
with 10-row W
Coil, large
with 10-row W
5
Coil, electric heat
Coil, integral face-and-
7
bypass
Face-and-bypass,
internal
Face damper
Humidifier
Moisture eliminator
Fan, horizontal
8
discharge
Fan, bottom front
8
discharge
Diffuser
Discharge plenum
9
Gas heat
Side inlet hood
(add to width)
Back inlet hood
(add to length)
Exhaust hood (add to
width or length)
Unit end panels
(add to length)
Note:
(1) Nominal airflow is based on 500 fpm through a nominal coil (i.e. 500 x unit size 8 = 4000 cfm). (2) Airflow @ 625 fpm through the flat filter (maximum
filter velocity) (3) Airflow is the maximum recommended velocity through a back inlet hood. (4) Size 3 mixing boxes without filters are 24.75 inches long.
(5) For sizes 3 - 57 blow-thru applications, electric heat sections require, at a minimum, a large section immediately downstream and a medium section
immediately upstream. (6) For size 66 blow-thru applications, electric heat sections require, at a minimum, a medium-large access section downstream and
a medium section immediately upstream. (7) IFB coil sections require a section immediately downstream: (at a minimum) a large section on size 3, medium
section for sizes 6 to 100. (8) Fan section weights include the heaviest fan with the largest ODP motor available.(9) Lengths and weights of gas heat sections
are with the largest capacity burner. Refer to the T-Series Air Handler Gas Heat Quick Select (CLCH-SLB005-EN) or the TOPSS selection program for detailed
dimensions.
CLCH-SVX06A-EN • T-Series Climate Changer Air Handler IOM