Trane Climate Changer T Series Installation Operation & Maintenance page 31

Table of Contents

Advertisement

Base Assembly
Figure 14. Joining base assembly
Threaded rod
Base sections
Panel Assembly
Figure 15. Panel Assembly
Seam cap
#10 Screw
CLCH-SVX06A-EN • T-Series Climate Changer Air Handler IOM
Flashing
Flat washers,
lockwashers and
1/2-inch nut
1. See drawing MS2998-3686 in the hardware package.
2. Leaving the paper backing on the tape, apply butyl tape
Raceway
Note: The seam cap should be cut to size to cover the seam and
3. Install the seam cap directly over the seam and tape. Attach
4. Caulk the gap between the top of the seam cap and the
Outer
Panel
Base
Butyl tape
1. See drawing MS2998-3686-0200 in the hardware
package.
2. Slide the 1/2-inch threaded rod through the hole in
each of the two joined base sections as shown in
Figure
14.
3. Install two flat washers, lock washer, and 1/2-inch nut
at each rod end. Tighten both nuts.
4. Install the flashing piece on the base assembly.
Secure in place with two 10-16 x 3/4-inch sheet metal
screws.
5. Repeat steps 1- 3 for the base assembly on the other
side of the unit.
(tape side down) along the length of the panel seam.
tape.
using 10-16 x 3/4-inch screws through all predrilled holes in
the cap.
bottom of the raceway.
Installation-Mechanical
31