Trane Climate Changer T Series Installation Operation & Maintenance page 32

Table of Contents

Advertisement

Installation-Mechanical
Hood (Back and Side) Installation
Inlet hoods should be installed after the unit has been set in place. They should not be
stacked on the unit as it is being hoisted. Mounting hardware and caulking tape for the
inlet hoods are located inside the unit. For installation complete the following:
Note: The hood assembly should be supported by chains, spreader bar, or other means
1. See drawing MS2999-5696 in the hardware package.
2. Apply the 1-inch butyl tape in a strip around the perimeter of the hood.
3. Using the lifting lugs, hoist the hood and center it over the panel opening as shown
4. Attach the hood to the unit with the 1/4-20 self-drilling screws provided. Use all holes
5. Attach the two hood angle supports (when provided) to the hood at one end and the
Figure 16. Hood and pipe cabinet installation
32
(see lifting instructions section) when installed to the unit. Mounting tape and
hardware are located inside the unit.
in
Figure
16.
drilled in the attachment flanges.
bracket on the unit as shown. Secure with 5/16-inch lock bolts and lock nuts and #10-
3/4 self-drilling screws.
T-Series Climate Changer Air Handler IOM • CLCH-SVX06A-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents