System Installation
HPC
+24VDC
Power
Supply
N or L2/N
VAC
L1
Earth
Varistor
(3 places)
76
Gemini GT6 Hardware Installation Guide
The next figure shows a typical EMC installation.
RS-232/485
Cable
VDC+
VDC–
Twisted at 3 twists
minimum per
inch (25 mm)
Mains
Filter
Motor
Cable
EMC Installation
If you mount the Gemini drive in an enclosure, terminate cable braids (screens) at
the entrance of the enclosure. However, the motor braid must be returned to the
drive's saddle clamp, not any other location.
Gemini
Drive
Bond braid to earthed panel.
Use R-clamp or bulkhead
clamshell clamp. (See
360° bonding drawing.)
Mount to earthed
metal panel, paint
removed from
mounting locations
Drive I/O Cable
Saddle clamp
braid; make loop
as short as
possible
I/O
Limits
GEM-VM50
Breakout Module
(enclosure mounted, or
not accessible to user)
Motor