Installing Optional Outdoor Temperature/Humidity Sensor
One optional outdoor temperature/humidity sensor (8301-090) can be installed. Follow the manufacturer's mounting
instructions. Use 18 gauge 5-conductor shielded cable to connect to controller. The maximum cable length to connect
the temperature/humidity sensor to the LC6000 is 98'.
1.
Connect wires from the 18 gauge shielded cable to terminals #65, #66, #67, #70 and #71.
Wire
TB#
Sensor
Mark
70
B12
71
ND
67
B11
66
GND
65
+VDC
46
47
48
49
50
51
52
2.
Connect the other end of the shielded cable to the sensor terminals. Be sure wires are connected to proper terminals
as shown in table above.
Manual 2100-713A
Page
24 of 44
Remote Outdoor Temperature/Humidity Sensor Installation
4
Remote Outdoor Temperature Sensor
5
Ground
1
Remote Outdoor Humidity Sensor: 0-10 VDC
3
Ground
2
+VDC
53
54
55
56
57
58
59
FIGURE 16
Description
60
62
61
64
63
68
67
72
66
65
70
69
71