General Information - Bard MULTI-TEC W18ABP Series Literature Assembly

Wall-mount air conditioner and heat pumps
Table of Contents

Advertisement

Air Conditioning System
This Bard air conditioning system is composed of
MULTI-TEC wall-mounted air conditioners matched
with an LC6000 supervisory controller, th-Tune single-
unit controller or PGD stand-alone display. If only one
wall-mounted air conditioner is being used, it can be
matched with either the LC6000 supervisory controller,
th-Tune or PGD (see Single Unit Operation on page
3 for information on the th-Tune and PGD). If more
than one wall mount is installed, the LC6000 controller
must be matched with the air conditioning units.
The wall-mount units are specifically engineered for
telecom/motor control center rooms.
LC6000-200 Series Controller and Accessories Included with Controller
(1) LC6000 Programmable Logic
Controller
Outside Air
Temperature/Humidity Sensor
Bard P/N 8301-090
One remote temperature/humidity sensor is included with the LC6000 controller. If the site in which the LC6000
1
controller will be used has more than one zone (maximum three zones per LC6000), additional remote temperature/
humidity sensors (one sensor per zone) will need to be purchased and installed in the additional zones. One
additional temperature-only sensor (Bard P/N 8301-058) may also be used in Zone 1 but will also need to be
purchased separately. Additional temperature/humidity sensors require field-supplied 5-wire 18 gauge shielded
cable. Temperature-only sensors require field-supplied 2-wire 18 gauge shielded cable.
NOTE: The LC6000 supervisory controller and
Controller
LC6000 controller and accessories shown below.
+
Optional Sensors:
Remote
Temperature/Humidity Sensor
Bard P/N 8403-079

GENERAL INFORMATION

MULTI-TEC wall-mount units are designed
specifically to work together. The controller
cannot run other brands of systems, nor can
other controllers run the MULTI-TEC wall-mount
units. They are a complete system, and must be
used together.
(1) TEC-EYE
Hand-Held Diagnostic Tool
TM
Bard P/N 8301-059
(1) Remote Temperature/Humidity Sensor
Bard P/N 8403-079
(1) 35' 5-Wire 18 Gauge Shielded Cable
(2) Communication EMI Filters
Bard P/N 8301-055
Temperature Only Sensor
1
Bard P/N 8301-058
1
Remote
Manual 2100-713A
Page
3 of 44

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents