FIGURE 38
Enable/Disable Zone 1 Remote Temperature Sensor
To enable/disable Zone 2 Remote Temperature:
1) Press MENU key to go to the Main Menu screen.
2) Use UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config;
press ENTER key.
4) Press UP or DOWN keys to scroll to Z2 Remote
Temp C9.
5) Press ENTER key to scroll to Enable (see
Figure 39).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
FIGURE 39
Enable/Disable Zone 2 Remote Temperature Sensor
To enable/disable Zone 3 Remote Temperature:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config;
press ENTER key.
4) Press UP or DOWN keys to scroll to Z3 Remote
Temp C10.
5) Press ENTER key to scroll to Enable (see
Figure 40).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
FIGURE 40
Enable/Disable Zone 3 Remote Temperature Sensor
To enable/disable Outdoor Air Humidity:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config;
press ENTER key.
4) Press UP or DOWN keys to scroll to Outdoor
Air Humid C11.
5) Press ENTER key to scroll to Enable (see
Figure 41).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
FIGURE 41
Enable/Disable Outdoor Air Humidity Sensor
To enable/disable Outdoor Air Temperature:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to IO Config;
press ENTER key.
Manual 2100-713A
Page
39 of 44