TABLE 6
Wall-Mount Unit Status Messages
Message
Unit disabled due to faulty
Invalid Model #
model number.
Unit is not currently communicating
Orphan Mode
with an LC6000 or th_Tune device.
Communication with th_Tune
th-Tune Online
device is established; unit in
standby (no current calls).
Communication with LC6000 is
LC Online
established; unit in standby (no
current calls).
Cont. Blower
Continuous blower is active.
Unit has been commanded off by
Off by th-Tune
the th_Tune.
Freecooling
Economizer is active.
Economizer and mechanical
Optimized Cool
cooling are active.
Cooling
Mechanical cooling is active.
Heating
Electric or mechanical heat is active.
Mechanical dehumidification or
Active Dehum
electric reheat dehumidification is
active.
Humidity is above the passive set
point; economizer disabled/blower
speed reduced. See Balanced
Passive Dehum
Climate Mode in MULTI-TEC
Service Instructions 2100-712.
Run Test
Run test in operation.
All functions/modes of operation
are disabled by one the following
Off by Alarm
alarms: Return Air, Emergency Off,
Unit Disable or Valid Model #.
Unit has been set to off by BMS
Off by BMS
system (Modbus); all functions/
modes of operation are disabled.
Unit is commanded off by LC6000;
Off by LC
all functions/modes of operation
are disabled.
Unit has been turned off in TEC-
Off by Keypad
EYE menu; all functions/modes of
operation are disabled.
Emergency vent mode is active.
Emergency Vent
See LC manual 2100-669.
Emergency Cool
Emergency cooling mode is active.
Emergency off mode is active. See
Emergency Off
LC manual 2100-669.
Description
TABLE 7
LC6000 Status Messages
Message
The LC6000 is ready and functioning
On
properly.
The LC6000 is being turned off by the
Off by BMS
Building Management System through
Modbus TCP/IP.
The LC6000 is turned off using the
Off by
(D. On/Off) Menu on the PGD. All
Keyboard
communicating units will be inactive.
The LC6000 is set to Comfort Mode.
This mode is used to temporarily
Comfort Mode
override heating/cooling setpoints and
maintain a default temperature of 72°F
for 60 minutes.
A high temperature has been sensed
in one or more zones. All available
Emergency
units in that zone are sent a command
Cooling
for emergency cooling. (Refer to unit
manual 2100-712 for emergency
cooling sequence.)
Input signal from an external device
at terminal DI2 (e.g., hydrogen
detector). Units that are equipped with
Emergency
a ventilation option and configured
Vent
will open the dampers at 100% with
the blower at full speed. (Refer to LC
manual 2100-669 for emergency vent
sequence.)
Description
Manual 2100-713A
Page
43 of 44