Bard MULTI-TEC W18ABP Series Literature Assembly page 81

Wall-mount air conditioner and heat pumps
Table of Contents

Advertisement

Model
W24ABPD00, D0Z
D05
D08
W24ABPF00, F0Z
F05
W30ABPD00, D0Z
D05
D10
W30ABPF00, F0Z
F07
F12
W36ABPD00, D0Z
D05
D10
W36ABPE00, E0Z
E06
E12
W36ABPF00, F0Z
F07
F12
Model
W24LBPF00, F0Z
F05
W30LBPF00, F0Z
F07
F12
W36LBPF00, F0Z
F07
F12
 Maximum size of the time delay fuse or "D" rated circuit breaker for protection of field wiring conductors.
 These "Minimum Circuit Amp" values are to be used for sizing the field power conductors.
 415/380-3 Electrical Ratings are 3-phase wye (star) systems requiring three (3) phase legs plus neutral and ground.
NOTE: The indoor and outdoor motors and 24V transformer primary are connected at 240V derived from one (1) phase leg
to neutral. This is internally connected and no field wiring required.
NOTE: All wiring must conform to NIC/EIC latest edition.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses
and conductor wires in accordance with the National Electrical Code and all local codes.
Manual 2100-713A
Page
18 of 44
TABLE 3A
Electrical Specifications − W**ABP Series − 50Hz Units
Operating
Rated Volts &
Voltage
Phase
Range
240/220-1
254-198
415/380-3 
456-342
240/220-1
254-198
456-342
415/380-3 
240/220-1
254-198
230/200-3
242-180
456-342
415/380-3 
TABLE 3B
Electrical Specifications − W**LBP Series − 50Hz Units
Operating
Rated Volts &
Voltage
Phase
Range
415/380-3 
456-342
415/380-3 
456-342
456-342
415/380-3 
Single Circuit
No. Field
Power
Circuits
Minimum Circuit
Ampacity
1
15
1
28
1
44
1
10
1
11
1
15
1
28
1
54
1
10
1
16
1
26
1
17
1
28
1
54
1
17
1
21
1
39
1
10
1
14
1
22
Single Circuit
No. Field
Power
Minimum Circuit
Circuits
Ampacity
1
10
1
11
1
10
1
16
1
26
1
10
1
14
1
22
Maximum External
Fuse or Ckt. Brkr.
20
30
45
15
15
20
30
60
15
20
30
25
30
60
25
25
40
15
15
25
Maximum External
Fuse or Ckt. Brkr.
15
15
15
20
30
15
15
25

Hide quick links: