CONTENTS Getting Other Information and Publications ..3 Sequence of Operation ........22 Balanced Climate Mode ........ 22 Wall Mount General Information ......4 Vent Connection Plug .......... 23 Air Conditioner Wall Mount Model Nomenclature ..4 Compressor Control Module ......... 23 Shipping Damage ..........
WALL MOUNT GENERAL INFORMATION AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE – MODEL SERIES CONTROL MODULES (See Spec. Sheet S3573) CAPACITY 18 – 1½ Ton COIL OPTIONS 24 – 2 Ton X – Standard 30 – 2½ Ton 1 – Phenolic Coated Evaporator 36 –...
5/8". Any grille that meets with 5/8" louver criteria may be used. It is recommended that Bard Return Air Grille Kits RG2 through RG3 or RFG2 through RFG3 be installed when no return duct is used. Contact distributor or factory for ordering information.
Inspect wall surfaces Bard recommends at least 2' between solid objects for obstructions that could hinder unit installation and return grilles or registers. Ductwork may be used to...
5/8". It is recommended that a airflow requirement of the equipment. Air Conditioning Bard Return Air Grille Kit is installed that is designed Contractors of America (ACCA) is an excellent guide specifically for the wall mount product. Contact the to proper sizing.
• Appropriate safety gear including gloves and safety 2. Locate and mark bolt hole locations and bottom glasses mounting bracket location. Install bottom mounting bracket with field-supplied fasteners to • 5/16" hex bit with drill driver wall if it is to be used (optional). Bracket must be •...
TABLE 1 Clearance Required for Service Access and Adequate Condenser Airflow Left Right Discharge Model Side Side Side W18A W24A 15" 20" W30A W36A W18L W24L 20" 15" W30L W36L NOTE: For side-by-side installation of two W**A models, there must be 20" between units. This can be reduced to 15"...
FIGURE 4 Electric Heat Clearance W30AB, W30LB, W36AB, W36LB NOTE 1: SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4" CLEARANCE TO COMBUSTIBLE SURFACES. WARNING Fire hazard. Maintain minimum 1/4" clearance between the supply air duct and combustible materials in the first 3' of ducting.
FIGURE 5 Wall Mounting Instructions WALL STRUCTURE See Figures 3A and 3B Mounting Instructions FACTORY SUPPLIED RAIN FLASHING. MOUNT ON UNIT BEFORE INSTALLATION SUPPLY AIR SUPPLY AIR SUPPLY AIR DUCT OPENING OPENING RETURN AIR RETURN AIR RETURN AIR OPENING OPENING OPENING BOTTOM MOUNTING WOOD OR STEEL SIDING...
FIGURE 7 Common Wall Mounting Installations Non-Ducted Installations Ducted Installations Unit is Unit is Ceiling Ceiling sealed to sealed to wall. wall. Supply Air Duct Adjustable Supply Grille Optional Dropped Ceiling Wall Wall Mount Mount Fixed Blade Unit Unit Fixed Blade Return Grille Return Grille Indoor Area Indoor Area...
Wiring – Main Power reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are: WARNING Tap: 240 Range: 253 – 216 Tap: 208 Range: 220 – 187 NOTE: The voltage should be measured at the field power connection point in the unit and while Electrical shock hazard.
TABLE 3 Ventilation Features (Optional) Additional Low Voltage Connections (if applicable) See ventilation instructions provided with unit for low voltage wiring. Terminal Unit Description Low Ambient Control (LAC) V Control Discharge Air Sensor, The low ambient control is a pressure switch that is Option Only 10K Ohm attached to the liquid line of the system and monitors...
TABLE 5 provided for the DDC controls option that indicates the indoor blower assembly needs to be serviced. Humidity Controls Compressor Current Sensor Part Number Predominate Features The compressor current sensor indicates when the 8403-038 SPDT switching, pilot duty 50VA @ 24V; compressor is operational by measuring amp draw.
Programmable Thermostat Connections Completestat Model #CS9B-THOA or Model #CS9BE-THOA W1/E Thermostat W1/E YO/D Bard #8403-060 Optional CO2 Controller Bard Part #8403-096 24VAC CO2 OUT TEMP-OUT Unit Low B/W1 Voltage Term. Strip 12-Pin Vent Plug ALL VENT OPTIONS PLUG IN HERE If not equipped with a ventilation option to plug in, a jumper plug must be installed.
Thermostat Connections Units With Dehumidification 8403-038 Mechanical Humidistat T4 Pro 8403-089 T6 Pro 8403-090 8403-092 8403-047 Electronic Humidistat Optional CO2 Controller Bard Part #8403-096 24VAC CO2 OUT TEMP-OUT Unit Low B/W1 Voltage Term. Strip 12-Pin Vent Plug ALL VENT OPTIONS PLUG IN HERE If not equipped with a ventilation option to plug in, a jumper plug must be installed.
All W**A/W**L wall-mounted air conditioner series Topping Off System Charge models are supplied with a remote reset for the high If a leak has occurred in the system, Bard and low pressure switch. If tripped, the pressure switch Manufacturing recommends reclaiming, evacuating...
The direction of rotation of the compressor may be easily be applied under any normal circumstances. changed by reversing any two line connections to the If the Bard air conditioning system is being set up unit. in a typical environment where 72°F is the lowest...
0.20" ESP (total including both supply and return the low pressure switch remains open for more than statics). Consult Bard Application Engineering for 2 minutes. the CCM will de-energize the compressor details prior to implementation. for the delay-on-break time. If the switch closes again, it will then restart the compressor.
FIGURE 10 8201-169 Compressor Control Module High Pressure Switch Compressor Contactor Output 18-30 VAC Input Alarm Output Y Input from Thermostat Common and High Pressure Switch Troubleshooting Light Delay-on-Break Time Adjustment Potentiometer Low Pressure Switch Brownout Ignore Time DIP Switches* * Turn on only one switch for that specific ignore time setting.
If the Motor Is Running higher than allowed, additional duct work is NOTE: Bard Models PA13242; PA13302; PA13362-A, -B; PA13422-A, -B, -C; PA13482-A, -B, -C; PA13602-A, -B, -C needed. 1. It is normal for the motor to rock back and forth contain the X13-Series Motors.
TROUBLESHOOTING GE X13-SERIES ECM2.3 ™ MOTORS CONT’D. 2. Initiate a demand from the thermostat and check the Model X13 Communication Diagnostics 2. If the motor has proper high voltage and ground at A. If the low voltage communication is not voltage between the common and the appropriate motor The X13 motor is communicated through 24 VAC low voltage the L/L1, G, N/L2 connections, then continue with...
Fan Blade Setting Dimensions R-410A Refrigerant Charge Shown in Figure 13 is the correct fan blade setting This unit was charged at the factory with the quantity of for proper air delivery across the outdoor coil. Refer to refrigerant listed on the serial plate. AHRI capacity and Table 9 for unit specific dimension.
TABLE 10 Cooling Pressure – Standard Airflow Air Temperature Entering Outdoor Coil °F Return Air Temp Model Pressure (DB/WB) Low Side 75/62 High Side Low Side W18A/L 80/67 High Side Low Side 85/72 High Side Low Side 75/62 High Side Low Side W24A/L 80/67...
TABLE 11 Cooling Pressure – Balanced Climate Airflow Air Temperature Entering Outdoor Coil °F Return Air Temp Model Pressure (DB/WB) Low Side 75/62 High Side Low Side W18A/L 80/67 High Side Low Side 85/72 High Side Low Side 75/62 High Side Low Side W24A/L 80/67...
TABLE 12 Electrical Specifications − W**AB Series Single Circuit Multiple Circuit Maximum Rated Minimum Field External Fuse Field Power Ground Maximum Field Model Volts Circuit Minimum Power Wire Size Wire Size & Phase External Power Ground...
TABLE 13 Electrical Specifications − W**LB Series Single Circuit Multiple Circuit Maximum Rated Minimum Field External Fuse Field Power Ground Model Volts Maximum Field Circuit Minimum Power Wire Size Wire Size External Power Ground &...
MED. thermostat or other controlling device. Each speed tap is programmed by Bard at the factory to different motor Speed Tap 5: Optional HI cooling & heating speed. torque settings (see Figure 14).
Dirty Filter Switch Dirty Filter Switch Adjustment 1. Apply power to the unit. 1. Disconnect all power to the unit. Remove control panel outer cover and upper front panel. 2. Turn the unit indoor blower on (energize R-G on low voltage terminal board). 2.
FIGURE 17 Adjusting Dirty Filter Switch TURN CLOCKWISE TO INCREASE RESTRICTION AMOUNT REQUIRED TO ACTIVATE THE SWITCH AND COUNTER-CLOCKWISE TO DECREASE RESTRICTION AMOUNT MIS-4086 B Manual 2100-689H Page 35 of 42...
TABLE 17 Maximum ESP of Operation Electric Heat Only W18A/L, Model W30A/L, W36A/L W24A/L Outlet FRONT FRONT Speed Single High -A0Z -A05 -A08 -A10 -A15 -B0Z -B06 -B09 -B15 -C0Z -C06 -C09 -C15 Values shown are for units equipped with standard 1"...