Tec-Eye Screen Structure And Password Level; Tec-Eye Acronyms; Status Screen; Information - Bard MULTI-TEC W18ABP Series Literature Assembly

Wall-mount air conditioner and heat pumps
Table of Contents

Advertisement

TABLE 1
LC6000/TEC-EYE Passwords (Defaults)
User
Technician
Engineer
Use UP or DOWN keys and ENTER key to enter password

TEC-EYE Screen Structure and Password Level

Quick Menu
Setpoints (Stand Alone Temperature Control)

Information

Alarm Log

Main Menu
A
System Config: A1-A11 User (2000)
B
Adv Sys Config: B1-B5 Technician (1313)
C
I-O Config: C1-C9 Technician (1313)
D
On/Off: User (2000)
E
Alarm Logs: User (2000)
F
Settings
Date/Time: Technician (1313)
Language: User (2000)
Initialization
Clear Logs: User (2000)
System Default: Engineer (9254)
Alarm Export: User (2000)
7 Day I/O Log: User (2000)
G Logout
In addition to the menu structure above, there are also
Status and Alarm screens.

TEC-EYE Acronyms

MAT – Mixed air temperature
RAT – Return air temperature
OAT – Outdoor air temperature
OAH – Outdoor air humidity
Blower – Indoor Blower Status
Damper – Free cooling damper position status
C1 – Compressor activate status
H1 – Heater Stage 1 status
H2 – Heater Stage 2 status
ODP – Calculated outdoor dew point
FC – Free cooling status
RN – Component run time in minutes in last hour
ST – Number of start requests in last hour

Status Screen

The Status screen is the default start-up screen and
also the return screen after 5 minutes of no activity.
The screen can be accessed any time by pressing the
ESCAPE button repeatedly.
The wall-mount unit address is displayed in the upper
right corner on the Status screen (see Figure 2). The
Status screen also shows the current date, time, return
air temperature, mixed air temperature, outdoor air
temperature, outdoor humidity and outdoor dewpoint
conditions. Blower, damper and unit status are also
displayed. See Table 2 for MULTI-TEC wall-mount unit
status messages.
2000
1313
9254
Invalid Model #
Orphan Mode
th-Tune Online
Off by th-Tune
Optimized Cool
Active Dehum
Passive Dehum
Off by Keypad
Emergency Vent
Emergency Cool
Emergency Off
TABLE 2
Wall-Mount Unit Status Messages
Message
Unit disabled due to faulty
model number.
Unit is not currently communicating
with an LC6000 or th_Tune device.
Communication with th_Tune
device is established; unit in
standby (no current calls).
Communication with LC6000 is
LC Online
established; unit in standby (no
current calls).
Cont. Blower
Continuous blower is active.
Unit has been commanded off by
the th_Tune.
Freecooling
Economizer is active.
Economizer and mechanical
cooling are active.
Cooling
Mechanical cooling is active.
Heating
Electric or mechanical heat is active.
Mechanical dehumidification or
electric reheat dehumidification is
active.
Humidity is above the passive set
point; economizer disabled/blower
speed reduced. See Balanced
Climate Mode on page 14.
Self Test
Self test in operation.
All functions/modes of operation
are disabled by one the following
Off by Alarm
alarms: Return Air, Emergency Off,
Unit Disable or Valid Model #.
Unit has been set to off by BMS
Off by BMS
system (Modbus); all functions/
modes of operation are disabled.
Unit is commanded off by LC6000;
Off by LC
all functions/modes of operation
are disabled.
Unit has been turned off in TEC-
EYE menu; all functions/modes of
operation are disabled.
Emergency vent mode is active.
See LC manual 2100-669.
Emergency cooling mode is active.
Emergency off mode is active. See
LC manual 2100-669.
Description
Manual 2100-712C
Page
7 of 38