These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest version), Article 310 for power conductor sizing.
Maximum size of the time delay fuse or "D" type circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to all local and national electrical codes.
* F14 only offered on W**A units.
CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attentionto Note 8 of Table 310 regarding Ampacity
Adjustment Factors when more than three conductors are in a raceway.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with all existing local codes.