Running in Orphan Mode

With the AC breakers turned on, each MULTI-TEC
wall-mount unit has the capability to run without the
LC6000 controller or PGD connected—this feature is
called orphan mode. This keeps the shelter between
60°F and 77°F (factory default settings) by the use of
the factory-installed return air sensor in each wall-
mount unit. In orphan mode, the wall unit uses a
continuous blower setting to circulate room air into
the return air inlet and uses the return air temperature
sensor to control room temperature.
The wall-mount unit can be turned on and off with
the TEC-EYE hand-held diagnostic tool. When ON is
chosen, the wall-mount unit will heat or cool. When set
to OFF using the TEC-EYE, the wall-mount unit will not
heat, cool or ventilate.
To turn the unit on or off with TEC-EYE:
1. Connect the TEC-EYE diagnostic tool to the control
board located in the unit.
2. Press MENU key to go to the Main Menu screen.
3. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
4. Press UP or DOWN keys to scroll to On/Off; press
ENTER key.
5. Press UP or DOWN keys to change value from On
to Off or from Off to On.
6. Press ESCAPE key several times to return to Main
Menu screen.
To verify or change the wall-mount unit cooling and
heating setpoints in orphan mode:
1. Connect the TEC-EYE diagnostic tool to the control
board located in the unit.
2. From the Status screen, press UP or DOWN key
until Quick Menu displays Setpoints (SET) icon.
Press ENTER key.
3. Press ENTER key to scroll to the selected choice
(see Figure 11).
4. Press UP or DOWN key on desired value until value
displays correctly.
5. Press ENTER key to save and scroll to next
parameter.
6. Press ESCAPE key until Main Menu screen is
displayed.

PRELIMINARY START UP

FIGURE 11
Cooling and Heating Setpoints
During installation, the ability to run in orphan mode
allows deactivation of one of the existing, older wall-
mount units, while keeping the shelter cool with the
other unit still operating. Once the first of the Bard
MULTI-TEC wall-mount units is installed, orphan mode
can be enabled early in the installation—keeping the
climate inside the shelter stable and the installers
comfortable while the remainder of the older equipment
is removed and the remaining Bard MULTI-TEC wall-
mount units and LC6000 controller are installed.
Additionally, should any or all of the MULTI-TEC wall-
mount units lose communication with the LC6000
controller (such as during maintenance), they will
continue to serve the shelter's needs until a repair can
be made.
NOTE: Screenshots shown in this manual reflect
default settings (when applicable).