Allowable Piping Length - Daikin VRV II Series Design, Installation & Testing Instructions

Hide thumbs Also See for VRV II Series:
Table of Contents

Advertisement

Appendix
7.3

Allowable Piping Length

7.3.1 Branch with refnet joint
(Connection of 8 indoor units Heat pump system)
When multiple
Between outdoor
Maximum
and indoor units
allowable
length
• Actual pipe length
Pipe length between outdoor and indoor units ≤ 150m
Example unit 8: a + b + c + d + e + f + g + p ≤ 150m
• Equivalent length
Equivalent pipe length between outdoor and indoor units ≤ 175m
(assume equivalent pipe length of refnet joint to be 0.5m, that of refnet header to be 1m,
calculation purposes)
• Total extension length
Total piping length from outdoor unit* to all indoor units ≤ 300m
Between outdoor branch and outdoor unit
(Only for RXYQ18 or more)
• Actual pipe length
Piping length from outdoor branch to outdoor unit ≤ 10m
(Approximately length: max 13m)
Between outdoor and indoor units
Allowable
• Difference in height
height
Difference in height between outdoor and indoor units (H1) ≤ 50m
length
(Max 40m if the outdoor unit is below)
Between indoor and indoor units
• Difference in height
Difference in height between adjacent indoor units (H2) ≤ 15m
Between outdoor and outdoor units
• Difference in height
Difference in height between outdoor unit (main) and outdoor unit (sub) (H3) ≤ 5m
• Actual pipe length
Allowable
Pipe length from first refrigerant branch kit (either refnet joint or refnet header) to indoor unit ≤ 40m
length after
Example unit 8: b + c + d + e + f + g + p ≤ 40m
the branch
110
One outdoor
unit installed
(RXYQ5 ~ 16)
First outdoor
outdoor units
installed
(RXYQ18 ~)
Branch with refnet joint
Outdoor unit
a
b
c
d
e
A
B
C
D
h
i
j
k
1
2
3
4
Indoor units (1-8)
Outdoor unit
branch
a
b
c
A
B
C
h
i
j
1
2
Indoor units (1-8)
*If the system capacity is RXYQ18 or more, re-read to
the first outdoor branch as seen from the indoor unit.
REFNET joint (C)
g
f
H1
E
F
G
l
m
n
5
6
7
H2
8
REFNET joint (A-G)
H3
g
d
e
f
E
F
G
D
k
l
m
n
3
4
5
6
7
H2
Outdoor unit
s
r
t
General Information
Si39-303
H1
P
8
r ≤ 10m
s ≤ 10m
t ≤ 10m