Refrigerant Piping
2. To avoid the risk of oil retention to the stopping unit side, always connect the shutoff valve
3. If the piping length between the outdoor unit-connecting pipe kits or between the outdoor
172
and the piping between outdoor units as shown in the figure A or figure B.
A
Prohibited pattern
to indoor unit
to indoor unit
Change to pattern 1 or pattern 2
Unit A Unit B
to indoor unit
to indoor unit
units exceeds 2 m, create a rise of 200 mm or more in the gas line within a length of 2 m
from the kit.
If 2 m or less
If 2 m or more
Piping between
outdoor units
to indoor
unit
A
B
B
Oil collects to the stopping outdoor unit.
Unit A Unit B
Unit C
to indoor unit
Oil collects to the outdoor unit C when the system stops.
Change as shown in the figure below.
to indoor unit
Piping between outdoor units
to indoor unit
Piping between
outdoor units
2m or less
Rising height:
200 mm or more
2m or less
2m or less
Unit C
Rising height:
200 mm or more
2m or less
Rising height:
200 mm or more
2m
or more
Rising height:
200 mm or more
Installation Manual
Si39-303