Capacity Correction Factor By The Length Of Refrigerant Piping (Reference) - Daikin FTXS-L Series Engineering Data

Hide thumbs Also See for FTXS-L Series:
Table of Contents

Advertisement

EDUS091128
7.2

Capacity correction factor by the length of refrigerant piping (Reference)

The cooling capacity and the heating capacity of the unit have to be corrected in accordance with the length of refrigerant piping — the
distance between the indoor unit and the outdoor unit.
<— line : cooling capacity>
<--- line : heating capacity>
7.2.1
09/12 Class
R-410A (09/12 class)
1
0.9
0.8
16.4
5
7.2.2
15/18 Class
1
0.9
0.8
16.4
5
Split Type Air Conditioners FTXS-L / FDXS-L Series
Range of the Refrigerant
Additional Charge
32.8
49.2
65.6
10
15
20
Piping length
R-410A (15/18 class)
Range of the Refrigerant Additional Charge
32.8
49.2
65.6
10
15
20
Piping length
(ft)
(m)
(R16253)
82.0
98.4
(ft)
25
30
(m)
(R16255)
Capacity Tables