Daikin VRV II Series Design, Installation & Testing Instructions page 103

Hide thumbs Also See for VRV II Series:
Table of Contents

Advertisement

Si39-303
Detailed Setting
1. Setting mode 1 (H1P off)
$
Procedure of Low
Noise Operation
and Demand
Control
2. Setting mode 2 (H1P on)
$
%
&
'
(
General Information
In setting mode 2, push the BS1 (MODE button) one time. → Setting mode 2 is entered and
H1P lights.
During the setting mode 1 is displayed, "In low noise operation" and "In demand control" are
displayed.
In setting 1, push and hold the BS1 (MODE button) for more than 5 seconds. → Setting
mode 2 is entered and H1P lights.
Push the BS2 (SET button) several times and match the LED display with the Setting No.
you want.
Push the BS3 (RETURN button) one time, and the present setting content is displayed.
Push the BS2 (SET button) several times and match the LED display with the setting
content (as shown below) you want.
Push the BS3 (RETURN button) two times. → Returns to $ .
Push the BS1 (MODE button) one time. → Returns to the setting mode 1 and turns H1P off.
Test Operation