Daikin VRV II Series Design, Installation & Testing Instructions page 78

Hide thumbs Also See for VRV II Series:
Table of Contents

Advertisement

Test Operation
4.4.1.6 Detailed Explanation of Setting Modes
Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
Setting
Contamination Light
Contamination Heavy
Ultra-Long-Life
When a Ultra-long-life filter is installed, the filter sign timer setting must be changed.
Filter Sign Setting
Setting Table
Fan Speed
By setting to "Set Fan Speed," you can switch the fan speed to the set fan speed when the
Changeover
heating thermostat is OFF.
When Thermostat
take the setup location into consideration.
is OFF
Setting Table
Auto Restart after
For the air conditioners with no setting for the function (same as factory setting), the units will be
left in the stop condition when the power supply is reset automatically after power failure reset
Power Failure
or the main power supply is turned on again after once turned off. However, for the air
Reset
conditioners with the setting, the units may start automatically after power failure reset or the
main power supply turned on again (return to the same operation condition as that of before
power failure).
For the above reasons, when the unit is set enabling to utilize "Auto restart function after power
failure reset", utmost care should be paid for the occurrence of the following situation.
Caution 1. The air conditioner starts operation suddenly after power failure reset or
2. In the service work, for example, turning off the main power switch during
72
Filter Specs.
Mode No.
Setting Switch No.
10 (20)
Since there is concern about draft if using "fan speed up when thermostat is OFF," you should
Mode No.
12(22)
the main power supply turned on again. Consequently, the user might be
surprised (with question for the reason why).
the unit is in operation, and turning on the switch again after the work is
completed start the unit operation (the fan rotates).
Standard
200 hrs.
100 hrs.
Setting Position No.
1
First Code No.
Second Code No.
3
Long Life
Ultra Long Life Filter
2,500 hrs.
10,000 hrs.
1,250 hrs.
5,000 hrs.
Setting
01
Long-Life Filter
02
Ultra-Long-Life Filter (1)
03
Setting
01
LL Fan Speed
02
Set Fan Speed
General Information
Si39-303