Daikin VRV II Series Design, Installation & Testing Instructions page 93

Hide thumbs Also See for VRV II Series:
Table of Contents

Advertisement

Si39-303
Push the SET button and match with the LEDs No. 1 - 15, push the RETURN button, and
enter the data for each setting.
#
ways of expressing are as follows:
#
General Information
Data such as addresses and number of units is expressed as binary numbers; the two
The No. 1 cool/heat unified address is expressed as a binary
9 797997
number consisting of the lower 6 digits. (0 - 63)
16
4
1
32
8
2
In $ the address is 010110 (binary number), which translates to
16 + 4 + 2 = 22 (base 10 number). In other words, the address is
22.
977 7979
The number of terminal blocks for No. 12 and 13 is expressed as
64
16
an 8-digit binary number, which is the combination of four upper,
No.12
128 32
and four lower digits for No. 12 and 13 respectively. (0 - 128)
977 7997
In % the address for No. 12 is 0101, the address for No. 13 is
4
1
0110, and the combination of the two is 01010110 (binary
No.13
8
2
number), which translates to 64 + 16 + 4 + 2 = 86 (base 10
number). In other words, the number of terminal block is 86.
See the preceding page for a list of data, etc. for No. 0 - 22.