Daikin VRV II Series Design, Installation & Testing Instructions page 195

Hide thumbs Also See for VRV II Series:
Table of Contents

Advertisement

Si39-303
Precautions when knocking out knock holes
!
!
!
!
Caution
!
!
!
Never connect 200V to the terminal block of the interconnecting wiring. Doing so will break the
entire system.
!
!
For the above wiring, always use vinyl cords with 0.75 to 1.25 mm
wires). (3 core wire cables are allowable for the cooler/heater changeover remote controller
only.)
Installation Manual
To punch a knock hole, hit on it with a hammer.
After knocking out the holes, we recommend you paint the edges and areas around the
edges using the repair paint to prevent rusting.
When passing electrical wiring through the knock holes, remove any burrs from the knock
holes and wrap the wiring with protective tape to prevent damage.
Use a power wire pipe for the power wiring.
Outside the unit, make sure the weak electric wiring (i.e. for the remote control, between
units, etc.) and the strong electric wiring do not pass near each other, keeping them at least
50 mm apart. Proximity may cause electrical interference, malfunctions, and breakage.
Be sure to connect the power wiring to the power wiring terminal block and secure it as
described in 7-4 Field line connection.
Inter-unit wiring should be secured as described in 7-4 Field line connection.
• Secure the wiring with the accessory clamps so that it does not touch the piping.
• Make sure the wiring and the electric box lid do not stick up above the structure, and close
the cover firmly.
The wiring from the indoor units must be connected to the F1/F2 (In-Out) terminals on the
PC board in the outdoor unit.
After installing the interconnecting wires inside the unit, wrap them along with the onsite
refrigerant pipes using finishing tape, as shown below.
1
5
Knockout hole
If there are any possibilities that
Burr
small animals enter the system
through the knock holes,
plug the holes with packing
materials (to be prepared onsite).
2
1. Liquid pipe
2. Gas pipe
3. Interconnecting wiring
3
4. Insulator
5. Finishing tape
4
Field Wiring
sheath or cables (2 core
2
189

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents