Arithmetic instructions
F36_DINC
Adds "1" to the 32-bit data specified by d if the trigger EN is in the ON-state. The result is stored in
Description
d.
Example value 131081
Bit
31 . . 28 27 . . 24 23 . . 20 19 . . 16
d
Result value 131082 if trigger is ON
Bit
31 . . 28 27 . . 24 23 . . 20 19 . . 16
d
This instruction also exists as a P instruction (for FP2/2SH, FP3/5, FP10/10SH PLC types), which
is only executed at the rising edge of the EN trigger. Select [Insert P instruction] from the
"Instructions" pane if you require a P instruction. To facilitate reuse, the instruction then appears
under "Recently used" in the pop-up menu. Press <Ctrl>+<Shift>+<v> within the programming
area to open the list of recently used elements.
Availability of F36_DINC (see page 1325)
PLC types
Data types
Variable
Data type
ANY32
d
Operands
For
d
Error flags
No.
IEC address
%MX0.900.11
R900B
%MX0.900.9
R9009
In this example the function has been programmed in ladder diagram (LD) and structured text
Example
(ST).The same POU header is used for all programming languages.
POU header
All input and output variables used for programming this function have been declared in the POU
header.
Body
When the variable start changes from FALSE to TRUE, the function is carried out.
360
32-bit increment
0 0 0 0
0 0 0 0
0 0 0 0
0 0 1 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 1 0
Function
32-bit area to be increased by 1
Relay
-
DWY DWR
DWL
DSV
Set
for an instant
for an instant
15 . . 12 10 . . 8 7 . . 4 3 . . 0
0 0 0 0
0 0 0 0
0 0 0 0
32-bit area
15 . . 12 10 . . 8 7 . . 4 3 . . 0
1 0 0 0
0 0 0 0
0 0 0 0
T/C
Register
DEV
DDT
DLD
DFL
If
 the calculated result is 0.
 the result exceeds the range of 32-bit
data (overflow).
1 0 0 1
1 0 1 0
Constant
-

Advertisement

Table of Contents