Huawei UA5000 Manual page 85

Environment monitoring
Hide thumbs Also See for UA5000:
Table of Contents

Advertisement

UA5000 Universal Access Unit
Environment Monitoring
4.
5.
6.
7.
8.
9.
10. Configure the load and battery high-temperature power-off parameters.
11. Configure the environment parameters.
Issue 01 (2012-08-17)
load off permit
battery off permit : permit
shunt quotiety
AC over alarm voltage
DC over alarm voltage
power module number: 3
module 0 address
module 1 address
module 2 address
Load high-temperature-off permit: permit
Load high-temperature-off temperature(C): 65
Battery high-temperature-off permit: permit
Battery high-temperature-off temperature(C): 50
----------------------------------------------------------------------------
huawei(config-if-power4845-0)#display power environment parameter
EMU ID: 0
parameter
----------------------------------------------------------------------------
AnalogID Name
0
Temperature
Current
1
Humidity
Current
----------------------------------------------------------------------------
DigitalID Name
0
-
2
-
4
-
6
-
----------------------------------------------------------------------------
The results show that the power, temperature, and humidity parameters have been
configured automatically in the system; however, certain parameters need to be modified,
and certain extended monitoring parameters need to be added.
Configure the battery charging parameters.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the power charge command.
Configure the battery management parameters.
huawei(config-if-power4845-0)#power battery parameter 0.15 60 1 75
Configure the temperature compensation coefficient of the battery.
huawei(config-if-power4845-0)#power battery temperature 80 -20 80
Configure the power supply load power-off and battery set power-off parameters.
huawei(config-if-power4845-0)#power off load-off-state forbid load-off-voltage
44
Configure the power distribution parameters.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the power supply-parameter command.
Configure the rectifier unit parameter.
huawei(config-if-power4845-0)#power battery-test auto-discharge-permit 180 0 2
46
huawei(config-if-power4845-0)#power temperature-off load-off-state forbid
load-off-temperature 70 battery-off-state permit battery-off-temperature 53
l Configure the temperature parameters.
huawei(config-if-power4845-0)#power environment temperature 68 -5 80 -20
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
: permit
load off voltage
battery off voltage : 43.000V
: 100A
: 280V
AC lack alarm voltage : 180V
: 58 V
DC lack alarm voltage : 45V
: 1
module 0 control state: On
: 2
module 1 control state: On
: No Configured
power environment configration
AlmUpper AlmLower TestHigh TestLow Unit
50
0
80
10
Available Level|DigitalID Name
1
|
1
|
1
|
1
6 EPS30-4815AF Monitoring Solution
: 43.500V
module 2 control state: -
55
-5
100
0
Available Level
1
-
3
-
5
-
type
C
%R.H.
1
1
1
79