UA5000 Universal Access Unit
Environment Monitoring
Indicators
Table 8-4
Table 8-4 Indicators on the rectifier module of the ETP4890 power system
Indicator
Power indicator
Alarm indicator
Fault indicator
Table 8-5
Table 8-5 Indicators on the monitoring module
Indicator
RUN
Issue 01 (2012-08-17)
NOTE
By default, the ETP4890 power system is installed with a monitoring module, which is capable of the
inband management, the COM port can not be used as a network port.
describes the indicators on the rectifier module of the ETP4890 power system.
Color
Green
Yellow
Red
describes the indicators on themonitoring module.
Color
Green
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 ETP4890 Monitoring Solution
Status
Steady on
Blinking
Off
Steady on
Blinking
Off
Steady on
Blinking
Off
Status
Off
Description
Normal
There is AC input,
and the PSU is in the
manual query status
No AC input
A protection
mechanism is
triggered. After the
fault is rectified, the
rectifier module can
be restored to the
normal state
Communication
between the PSU and
the SMU is disrupted
Normal
An unrecoverable
fault occurs
Software is being
loaded
Normal
Description
The monitoring
module is faulty or
there is no DC power
input